SitePro S8 40kVA
Fig. 7.1-2 LEDs on synoptic diagram
Examples of typical scenarios in the synoptic diagram:
Load supplied by inverter
Load supplied by manual bypass Q2
Modifications reserved
OPM_SPE_XXX_10K_40K_8GB_V020.doc
UPS Model
Battery level LED
All LED light indicate a battery autonomy of 100%.
LED A
Fixed:
Blinking:
LED A, B
Indicate a battery autonomy between 26% and 50%.
LED A, B, C
Indicate a battery autonomy between 51% and 99%.
Min:
Battery autonomy time in minutes estimates with actual load.
Load level LED
All LED Off indicate a load status at ≤25%.
LED A
LED A, B
LED A, B, C
LED A, B, C, D
LED D blinking
UPS series number
indicates a battery autonomy between 6% and 25%.
indicates a battery autonomy ≤5%.
Indicates a load level between 26% and 50%.
Indicate a load level between 51% and 75%.
Indicate a load level between 76% and 100%.
Indicate a load level between 101% and 124%.
Indicates a load level ≥125%.
LEDs on synoptic diagram
LED 1
LED 2
LED 3
LED 4a
LED 4b
LED 5
LED 6
LED 7
LED 8
LED 9
LED 10
Load supplied by automatic bypass
Load supplied by battery
UPS nominal rating (kVA)
Input mains rectifier
Input mains bypass
Rectifier ON
Discharging battery
Charging battery
Inverter ON
Load on inverter
Q1 closed
Load on automatic bypass
Manual Bypass Q2 ON
Load on UPS
Page 45/99