GE 8 Series Operating Manual page 38

Table of Contents

Advertisement

JP2
JP1
JB-1
Terminal units
On the parallel bus PCB P34 – Bus Interface (IM0048), of the first and last units (terminal) of the
Parallel System the Jumpers JP1, JP2, JP3 and JP4 must be inserted.
JP2
JP1
JB (2)
JB (1)
Intermediate units
On the parallel bus PCB P34 – Bus Interface (IM0048) of the intermediate units of the Parallel System
the Jumpers JP1, JP2, JP3 and JP4 must be removed.
NOTE !
In a Parallel System composed of 2 or more units, only the first and last units (having
1 input JA and JB free) have the Jumper JP1, JP2, JP3 and JP4 inserted on parallel bus
PCB "P34 – Bus Interface (IM0048)" (see Fig. 5.9.2-2/3).
Modifications reserved
OPM_SPE_XXX_10K_40K_8GB_V020.doc
JP3
JP4
JA-1
Fig. 5.9.2-2 Bus connection on terminal units
JP3
JP4
JA (2)
JA (1)
Fig. 5.9.2-3 Bus connection on intermediate units
P11
J62
J52
B
A
P13
P3
P11
J62
J52
B A
P13
P3
Operating Manual SitePro 10-15-20-30-40 kVA / S8
Page 38/99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents