6. Set the most important parameters to suit your application.
– Minimum speed - factory setting 0 [rpm]
– Maximum speed - factory setting 1500 [rpm]
– The ramp-up and ramp-down times define the maximum motor acceleration when the
– OFF3 ramp-down time sets the ramp-down time from the maximum speed down to
SINAMICS G120 Smart Access
Operating Instructions, 04/2018, A5E43332487
The minimum speed is the lowest speed of the motor independent of the speed
setpoint.
The inverter limits the motor speed to the maximum speed.
speed setpoint changes. The ramp-up and ramp-down times are derived from the time
between motor standstill and the maximum speed, or between the maximum speed
and motor standstill.
zero speed for the OFF3 command.
Standard Web pages
5.4 Quick commissioning
31