PVI 23TL, 28TL Installation and Operation Manual (Rev J)
9.2.7 Power Dispatch
"ActivePower" and "PowerFactor" parameters can be set up through the LCD as well as remotely.
NOTE: These parameters are only adjustable with permission from the local utility.
NOTE: When prompted for a password, enter the following: UP, DOWN, UP,
DOWN, then ENT.
NOTE: It is often common at sites with High AC voltage above 1.05p.u that the
Utility would like to modify the power factor to reduce the voltage at the point of
common coupling. This can be done by setting the inverter to absorb vars. For the
PVI 23-28TL this can be achieved by setting the inverter to a negative value. For
example, one would set the power factor to -0.95 which will help reduce the AC
voltage at site by allowing the inverter to absorb vars.
If you are interested in enabling these features or in further understanding their capabilities,
please contact us at
support@solectria.com
DOCR-070365-J
5 Dispatch
Figure 9.5 – Active Power and Power Factor Settings
ActivePower(%)
100.0
PowerFactor
1.000
for more details.