Internal H1 Extension - Viessmann VITODENS 200-W Type B2HA Technical Manual

Wall mounted gas condensing boiler
Hide thumbs Also See for VITODENS 200-W Type B2HA:
Table of Contents

Advertisement

Control units
(cont.)

Internal H1 extension

Part no. 7498513
PCB for installation in the control unit.
Using the extension enables the following functions to be achieved:
Function
– Connection of an external safety solenoid valve (LPG)
And one of the following functions:
– Connection of a heating circuit pump for a directly connected heating circuit
– Connection of a central fault message
– Only for Vitotronic 200, type HO1B:
Connection of a DHW circulation pump
Power supply for DHW circulation pump
DHW circulation pumps with their own internal control unit must be
connected to a separate power supply. Mains connection via the
Vitotronic control unit or Vitotronic accessories is not permissible.
Internal H2 extension
Part no. 7498514
PCB for installation in the control unit.
Using the extension enables the following functions to be achieved:
Function
– External extractor interlock
And one of the following functions:
– Connection of a heating circuit pump for a directly connected heating circuit
– Connection of a central fault message
– Only for Vitotronic 200, type HO1B:
Connection of a DHW circulation pump
Power supply for DHW circulation pump
DHW circulation pumps with their own internal control unit must be
connected to a separate power supply. Mains connection via the
Vitotronic control unit or Vitotronic accessories is not permissible.
AM1 extension
Part no. 7452092
Function extension inside enclosure for wall mounting.
Using the extension enables up to two of the following func-
tions to be achieved:
■ Switching the DHW circulation pump (only with the Vitotronic 200,
type HO1B)
■ Switching the heating circuit pump for a directly connected heating
circuit
Power supply for DHW circulation pump
DHW circulation pumps with their own internal control unit must be
connected to a separate power supply. Mains connection via the
Vitotronic control unit or Vitotronic accessories is not permissible.
0
1 8
5 8
VITODENS 200-W
Rated breaking capacity of the relay output
Specification
Rated voltage
Rated frequency
Rated breaking capacity of the relay output
Specification
Rated voltage
Rated frequency
Specification
Rated voltage
230 V~
Rated frequency
50 Hz
Rated current
4 A
Power consumption
4 W
Rated relay output break-
2(1) A, 250 V~ each, total max. 4 A~
ing capacity
Safety category
I
IP rating
IP 20 D to EN 60529, ensure through
design/installation
Permissible ambient temperature
– Operation
0 to +40 °C
Installation in living spaces or boiler
rooms (standard ambient conditions)
– Storage and transport
–20 to +65 °C
1(0.5) A 250 V~
2(1) A 250 V~
230 V~
50 Hz
6(3) A 250 V~
2(1) A 250 V~
230 V~
50 Hz