Viessmann VITODENS 200-W Type B2HA Technical Manual page 27

Wall mounted gas condensing boiler
Hide thumbs Also See for VITODENS 200-W Type B2HA:
Table of Contents

Advertisement

Vitodens 200-W
(cont.)
Circulation pump VI PARA 30/1-12
Rated voltage
V~
Power consumption
– max.
W
– min.
W
Variable speed (Δp constant or Δp variable), fully wired.
Residual head of the circulation pump
1200
120
1100
110
1000
100
900
90
800
80
700
70
600
60
500
50
400
40
300
30
200
20
100
10
0
0
0
1000
Flow rate in l/h
Curve
Pump rate, circulation pump
A
B
C
D
E
F
Adjust the functioning of the circulation pump during commissioning
Hydraulic connection/connection requirements
Single boiler system with:
– Heating circuit without mixer
– Connection without low loss header and without heating
water buffer cylinder
Single boiler system with connection of the heating circuits
to the heating water buffer cylinder
VITODENS 200-W
F
E
D
C
B
A
2000
3000
4000
5000
50 %
60 %
70 %
80 %
90 %
100 %
Control unit setting
Coding address/group
– Max. pump speed:
– Min. pump speed:
For further details, see following diagram
and chapter "Heating circuit ..." under
code 2.
30:0/boiler/2
230
310
16
6000
7000
8000
9000
E6: ... /heating circuit
E7: ... /heating circuit
Circulation pump setting
Ext. In
Ext. In
2
2
6
6
12
12
Ext. In
2
2
6
6
12
12
Recommended for Δt = 15 K
= 3 ≙ 6.87 m
– 120 kW:
3
/h
= 6 ≙ 8.60 m
– 150 kW:
3
/h
VIESMANN
1
27