The SOLECTRIA XGI is compatible with SolrenView and third-party Data Acquisition Systems (DAS). When
using SolrenView monitoring no additional hardware is required. When connecting with third-party monitoring
providers, Ethernet connections must be used; RS485 is not supported.
When integrating SOLECTRIA XGI inverters with third-party monitoring platforms, one of the following methods
MUST be employed in order for the third-party DAS to reach each inverter as an Endpoint Device; 1. Port
forwarding, 2. Static Routing (discussed in detail in Section 5.7). Be sure to consult with the monitoring
provider before installation.

Third-Party Data Acquisition System (DAS) Connection

Ethernet Only Connection: The XGI 1000 series inverter only supports Ethernet connections to a third-party
DAS.
Connect the third-party DAS to the onsite LAN, outside of the Cluster LAN(s). Connecting a third-party DAS
inside the Cluster LAN will block communication to the DAS outside of the Cluster LAN.
If DHCP is not enabled on the LAN, a static IP assignment for the GUI must be configured. When using DHCP
consider using a reserved DHCP address.
To allow a third-party DAS (or any other device) to access inverters within a cluster(s) and treat all inverters as
Endpoint Devices, Port Forwarding or Static Routing must be used.
DOCR-071081-B
Cluster LAN
- XGI Inverters Only -
INV 49
INV 2
Figure 5-4 Networking with Other Devices
®
XGI 1500 DCG Series Inverters
- All other Ethernet devices -
INV 1, Gateway
Inverter
Firewall
NOTICE !
35 of 74
LAN
Modem or
Internet
Gateway
Other
Device
Other
Device
Internet