Parameters - Emerson Copeland Scroll XFAL Series Installation And Reference Manual

1.5 to 6 hp outdoor refrigeration unit
Table of Contents

Advertisement

13. Parameters

Label
Current Suction Pressure (PSIG)
Cin /
Compressor cut in pressure set point (PSIG)
CoU /
Compressor cut out pressure set point (PSIG)
rEF /
Refrigerant Selection for Regulation
idF /
interval between defrost cycles (hour)
MdF /
Maximum length for defrost (min)
EdF /
Ld1 /
Workday defrost start 1 (hour)
Ld2 /
Workday defrost start 2 (hour)
Ld3 /
Workday defrost start 3 (hour)
Ld4 /
Workday defrost start 4 (hour)
Ld5 /
Workday defrost start 5 (hour)
Ld6 /
Workday defrost start 6 (hour)
Min /
Hr /
MdY /
Mon /
YEr /
PAS /
P1F /
Lod /
Ambient temperature required to initiate low
LAS /
LMO /
Low ambient minimum on time (sec)
© 2016 Emerson Climate Technologies, Inc.
Description
Default Display Value
Adjustable in Programming Menu
Low Side Control
Defrost interval mode
Real Time Clock
Current minute
Current hour
day of month
month
year
Enter into PR2 level
Adjustable from Advanced Options Menu
Probe Configuration
Probe P1 calibration (PSIG)
Remote Display visualization
ambient on time (°F)
Default
Compressor
25.0
15.0
R404A
8
45
in
6:00
13:00
21:00
nu
nu
nu
Password
321
0.0
Display
P1
Compressor
-20
6
32
AE5-1412 R1
Range
Cou - 135
0 - Cin
All unit Refs
0 - 120
0 - 255
nu, in, RTC
nu, 0:00 - 23:50
nu, 0:00 - 23:50
nu, 0:00 - 23:50
nu, 0:00 - 23:50
nu, 0:00 - 23:50
nu, 0:00 - 23:50
0 - 59
0 - 23
1 - 31
1 - 12
0 - 99
(blank)
-12.0 - 12.0
P1 - P7
-40 - 230
0 - 255