Braking The Axes By Entering An Additional Braking Ramp; Braking The Spindle/Spindles By Entering The Braking Power - HEIDENHAIN iTNC 530 HSCI Technical Manual

Hide thumbs Also See for iTNC 530 HSCI:
Table of Contents

Advertisement

Braking the axes by
entering an
additional braking
ramp
Braking the
spindle/spindles by
entering the
braking power
July 2013
In this strategy, the braking ramp to be used in an emergency stop is entered.
Set the axis braking ramp for an emergency stop:
Enter as a minimum value in
Use the emergency stop to brake the axis from rapid traverse.
Increase the value entered in MP2590.x until the braking time is as short as
possible and the mechanics of the axis are not overloaded.
If the value entered is too small, i.e. if braking is too slow, the axis brakes at
the acceleration defined in MP1060.x.
Once the value for MP2590.x has been determined and entered, the braking
process at this setting must be checked. You must ensure that simultaneous
braking of all axes does not lead to a switch-off due to overload of the
inverters. The nearer the determined braking ramp is to the emergency stop
ramp, the greater the resulting load on the inverters is.
Note
The value entered in MP2590.x refers to the motor speed, meaning the ball
screw pitch is not considered.
MP2590.x
Braking ramp in an emergency stop
Input:
0.001 to 999.999 [min
0: Function inactive
In this strategy the maximum braking power for braking the spindle/spindles
in an emergency stop or power failure is entered.
If power limiting (MP2392.x) is used in normal operation, then the maximum
braking performance is limited to the lower of the two values from the power
limiting and the braking power.
Example:
Function
Power limiting (MP2392.x)
Maximum braking power
(MP2390.x, MP2394.x)
Limiting the braking
performance to
6.8 The control loop
MP1060.x 60
MP2590.x
------------------------------------- -
=
MP1054.x
–1
/ms]
Case 1
Case 2
10 kW
5 kW
5 kW
10 kW
5 kW
5 kW
.