Zone Registers - Omega DP606A User Manual

Universal 6/12 channel 1/4 din panel meter
Table of Contents

Advertisement

7
Modbus Register Assignments
Section 7.4 - Zone Registers
The zone specific registers are repeated
Zone 1 Register Base = 0x200
Zone 2 Register Base = 0x280
Zone 3 Register Base = 0x300
Zone 4 Register Base = 0x380
Zone 5 Register Base = 0x400
Zone 6 Register Base = 0x480
Zone 7 Register Base = 0x500
Zone 8 Register Base = 0x580
Zone 9 Register Base = 0x600
Zone 10 Register Base = 0x680
Zone 11 Register Base = 0x700
Zone 12 Register Base = 0x780
Index
Base + 0x00
Base + 0x02
Base + 0x04
Base + 0x05
Base + 0x06
Base + 0x07
Base + 0x08
Base + 0x09
Base + 0x0a
Base + 0x0c
Base + 0x0e
Base + 0x10
Example:
Current Scale High register for Zone 7
Index = 40,000 + Base + Index = 40,000 + 0x500 + 0x0a = 41290
25
Mnemonic
Setpoint High
Setpoint Low
Alarm 1 Mode
Alarm 1 Latch
Alarm 1 Status
Alarm 2 Mode
Alarm 2 Latch
Alarm 2 Status
Current Scale High
Current Scale Low
Voltage Scale High
Voltage Scale Low
Table 14 - Zone Registers
Type
Access
F
RW
Setpoint High for alarm
F
RW
Setpoint Low for alarm
R
RW
Enumerated alarm mode
R
RW
Enumerated setting toggle
R
RW
Enumerated alarm status
R
RW
Enumerated alarm mode
R
RW
Enumerated setting toggle
R
RW
Enumerated alarm status
F
RW
High scale reading for current input
F
RW
Low scale reading for current input
F
RW
High scale reading for voltage input
F
RW
Low scale reading for voltage input
Description