Section 5.17 - Function C/D - Scaling
Functions C and D set the scaling for the mA and mV input. Function C sets the
Low Scale and Function D sets the High Scale. The scaling factors for mA and mV
are separate so the values corresponding to the input type selected in Function 7 are
shown.
By default the scaling is set to display the measurement in mA/mV.
Scaling factors are applied independently for each zone. The current zone being
modified is displayed in the Zone Display. Enter the value to be displayed at 4mA or
0V in Function C and the value to be displayed at 20mA or 1V in function D. Values
between the two points are linearly interpolated.
Function
Increment the flashing digit
Selects the next digit, causing it to flash
Changes the decimal point
Stores the current scaling factor for the indicated zone
advances to the next zone.
Stores all values and returns to Function Select mode
D
C
Input Current / Voltage
Figure 7 - Process Input Scaling