Using Single-Stranded Cables; Internal Equipotential Bonding; Stepless Mating Face For The Seal In The Terminal Box Cover - Siemens SIMOTICS FD 1MH1 Operating Instructions & Installation Instructions

Low-voltage motor
Table of Contents

Advertisement

6.5.8

Using single-stranded cables

High temperatures from induced eddy currents
With high currents and where several single-stranded cables are used instead of multiple-
stranded cables, high temperatures can result in the cable entry area due to induced eddy
currents. A short-circuit and an explosion may occur. This can result in death, serious injury,
or material damage.
● After commissioning, ensure that the temperature limits of the connected power cables
● Use a cable entry plate made of non-ferrous metal.
6.5.9

Internal equipotential bonding

Between the ground terminal in the terminal box enclosure and the machine enclosure, the
fixing screws of the terminal box serve as PE conductor connection.
Between terminal box cover and terminal box enclosure, the cover fixing screws serve as
equipotential bonding.
A special external ground conductor is only installed if, for example, flat seals are mounted
without additional support.
When performing any installation work, you must always take care to ensure that all
equipotential bonding measures remain effective.
6.5.10

Stepless mating face for the seal in the terminal box cover

The sealing face of the terminal box cover is formed by the terminal box enclosure and the
cable entry element. Therefore make sure these parts are correctly aligned, so as to ensure
the seal and hence the degree of protection.
Align the cable entry support and the cable entry plate to the terminal box enclosure so that
the sealing surface between the terminal box and the terminal box cover form a flat face. There
must be no steps in the sealing area.
SIMOTICS FD 1MH1
Operating Instructions 08/2017
WARNING
are not exceeded during operation. This temperature effect can be reduced by altering
the conditions at the entry points or by using modified cable entry plates after consultation
with the manufacturing plant.
Electrical connection
6.5 Inserting and routing the cables
99

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotics fd 1mq1Simotics fd 1ll1

Table of Contents