Specification - Wolf CFL-WRG Installation And Maintenance Instructions Manual

Comfort slimline ventilation unit
Table of Contents

Advertisement

Specification

Size
Max. air volume
at available ext. pressure, supply air
at available ext. pressure, extract air
Heat recovery rate
Height
Width
Length
Control panel width
Internal duct connection dimensions
Weight
Motor data for each fan
Mains voltage
Frequency
Max. power consumption
Max. current consumption
Speed
Energy efficiency class
IP rating
Protection class
Power cable
Supply voltage
Cable cross-section
On-site fuse
Power cable
Supply voltage
Cable cross-section
On-site fuse
3065065_201704
5. Specification
CFL
10-WRG
m³/h
1000
Pa
270
Pa
295
%
> 90
A mm
367
B mm
1017
C mm
1322
D mm
115
mm
409 x 247
kg
130
CFL
10-WRG
V
1 x 230 V
Hz
50 / 60
W
480
A
2.1
rpm
2970
IE 4
IP 54
Iso B
CFL
10-WRG-PWW
V
1 x 230 V
mm²
3 x 1.5 mm²
A
16 A
CFL 10-WRG-E-Reg.
V
1 x 230 V
mm²
3 x 1.5 mm²
A
16 A
15-WRG
22-WRG
1500
2200
380
220
395
170
> 90
> 90
367
411
1423
1830
1322
1525
115
115
612 x 247
815 x 291
160
240
15-WRG
22-WRG
1 x 230 V
1 x 230 V
50 / 60
50 / 60
750
715
3.3
3.1
3450
2800
IE 4
IE 4
IP 54
IP 54
Iso B
Iso B
15-WRG-PWW
22-WRG-PWW
3 x 400 V
3 x 400 V
5 x 1.5 mm²
5 x 1.5 mm²
16 A
16 A
15-WRG-E-Reg.
22-WRG-E-Reg.
3 x 400 V
3 x 400 V
5 x 2.5 mm²
5 x 2.5 mm²
20 A
20 A
32-WRG
3200
600
610
> 90
495
1932
1932
-
866 x 354
340
32-WRG
3 x 400 V
50 / 60
1650
2.5
3140
IE 4
IP 54
Iso B
32-WRG-PWW
3 x 400 V
5 x 2.5 mm²
20 A
32-WRG-E-Reg.
3 x 400 V
5 x 6 mm²
35 A
9

Hide quick links:

Advertisement

Table of Contents
loading