Before starting any maintenance work, switch OFF the mains isolator and safeguard against unauthorised reconnection.
If the isolator is switched back on unintentionally, maintenance staff or others in the vicinity could be at risk from
rotating parts.
Wait for the fans to come to a complete standstill before opening the doors (approx. 2 minutes). Also observe the
clearly visible warning on the unit. When the doors are opened, negative pressure may draw in loose objects, which
could destroy the fan or even cause a risk to life.
Voltage is still present at terminals and connections of the EC fans even when the unit has been shut down.
This means there is a risk of electric shock that could result in injury or death.
- Do not touch the EC fans for five minutes after disconnecting the power across all poles.
- Use a rubber mat if working on the unit when it is electrically charged.
CFL 10 / 15 / 22
Doors can be removed
completely after taking
out the hinge pin.
CFL 32
3065065_201704
10. Maintenance shutdown
Open inspection
doors using a
quadrant key
Open the inspection cover
using a quadrant key
1
2
1
4
3
I
I
2
>
min
xx/xx
6074238
Doors can be removed
completely after taking
out the hinge pin.
23