4 Wire RS485 (Full Duplex)
Characteristics of a 4 wire, or Full Duplex RS485 connection include:
• Bus cable with a max. length of 1200 m (4000 ft) depending upon cable quality and speed of the data
• Stub cable of max. 5 meters
• Master/slave applications
• Inverted line is generally indicated by the index "A" or "-"
• Non-inverted line designated as "B" or "+"
• Except for trivially short point to point connections, terminating resistors are generally required.
• A ground wire is also normally used in addition to what is shown in
Figure 15: 4 Wire RS485 (Full Duplex)
1
2
3
4
Wiring Recommendations for RS-485 Networks:
• Typically Category 5 Ethernet cable is suitable for RS-485.
• Shielded cable is desirable and the shield should be grounded at on end if it is used.