4. Position isolator pads or spring isolators beneath
the chiller feet (refer to
instructions).
N N o o t t e e : : Follow instructions provided by the spring
isolator manufacturer, being careful to not
damage isolator adjustment screw.
5. Once the isolators are in place, lower the chiller—
working from end to end—in small increments to
maintain stability.
6. When lift is complete, detach the clevis connections
and safety chain.
CVHH-SVX001G-EN
"Unit Isolation," p. 24
for
I I n n s s t t a a l l l l a a t t i i o o n n : : M M e e c c h h a a n n i i c c a a l l
Figure 8. Typical rigging arrangements
15 feet
(4.6 m)
minimum
effective
length
Safety
chain or
cable
Jack slots
23