Technical specifications
6.1 Technical specifications
Article number
Smoothing of measured values
Number of smoothing levels
•
parameterizable
•
Encoder
Connection of signal encoders
for voltage measurement
•
for resistance measurement with two-wire
•
connection
for resistance measurement with three-wire
•
connection
for resistance measurement with four-wire
•
connection
Errors/accuracies
Linearity error (relative to input range), (+/-)
Temperature error (relative to input range), (+/-
)
Crosstalk between the inputs, min.
Repeat accuracy in steady state at 25 °C (rela-
tive to input range), (+/-)
Operational error limit in overall temperature
range
Voltage, relative to input range, (+/-)
•
Resistance, relative to input range, (+/-)
•
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)
•
Resistance, relative to input range, (+/-)
•
Interference voltage suppression for f = n x (f1 +/-
1 %), f1 = interference frequency
Series mode interference (peak value of
•
interference < rated value of input range),
min.
Common mode voltage, max.
•
Common mode interference, min.
•
Isochronous mode
Isochronous operation (application synchro-
nized up to terminal)
50
6ES7134-6JD00-0CA1
4; None; 4/8/16 times
Yes
Yes
Yes
Yes
Yes
0.01 %; ±0.1 % for resistance thermometers and
resistance
0.0009 %/K; ±0.005 % / K at thermocouple
-50 dB
0.05 %
0.1 %
0.1 %
0.05 %
0.05 %
70 dB
10 V
90 dB
No
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
Manual, 09/2018, A5E03573289-AE