Siemens SIMATIC ET 200SP Manual page 27

Analog input module
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameters/address space
4.2 Parameters
Parameter
Low limit 2
4
Potential group
Diagnostics: Missing supply voltage L+: Detection per module or alarm per channel
1
Interference frequency suppression: Interfering signals at 400 Hz are automatically included in the filtering at 50 Hz.
2
The settings in the "Interference frequency suppression" parameter have a direct effect on the conversion time of the
3
channel. The analog value is therefore also affected by additionally set filtering via the "Smoothing" parameter.
Due to the limited number of parameters of a maximum of 244 bytes per ET 200SP station with a PROFIBUS GSD
4
configuration, the parameter assignment options are restricted. The parameter length of the I/O module is 13 bytes with
PROFIBUS GSD configuration. If necessary, you can set this parameter with data record 128, see Appendix "Parameter
data record".
Only for configuration with PROFIBUS GSD file: The set reference junction is used with the additional parameter "Kx
5
Reference junction activated" in the case of "Enable". In the case of "Disable", "No reference channel mode" is used for
RTD and "Fixed reference temperature" is used for TC.
For 2-wire connection only
6
Note
Unused channels
"Deactivate" unused channels in the parameter assignment to improve the cycle time of the
module.
A deactivated channel always returns the value 7FFF
26
Value range
Value
Use potential group of the
left module (module
plugged into a dark-
colored BaseUnit)
Enable new potential
group (module plugged in-
to light-colored BaseUnit)
Default
Reconfigu-
ration in
RUN
-2000
Yes
Use potential group
No
of the left module
.
H
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
Scope with configuration
software, e.g., STEP 7 (TIA
Portal)
GSD file
GSD file
PROFINET
PROFIBUS
IO
DP
Channel
-
Module
Module
Manual, 09/2018, A5E03573289-AE

Hide quick links:

Advertisement

Table of Contents
loading