Parameters/address space
4.2 Parameters
Parameter
Type/range of meas-
urement
Type/range of meas-
urement
Type/range of meas-
urement
22
Value range
Deactivated
•
Voltage ±50 mV
•
Voltage ±80 mV
•
Voltage ±250 mV
•
Voltage ±1 V
•
Resistor
(2-, 3-, 4-wire connection)
150 Ω
•
300 Ω
•
600 Ω
•
3 kΩ
•
6 kΩ
•
Resistor (2-wire connection)
PTC
Thermal resistor
(2, 3, 4-wire connection)
Pt 100 climatic range
•
Pt 200 climatic range
•
Pt 500 climatic range
•
Pt 1000 climatic range
•
Thermal resistor
(2, 3, 4-wire connection)
Pt 100 standard range
•
Pt 200 standard range
•
Pt 500 standard range
•
Pt 1000 standard range
•
Default
Reconfigu-
ration in
RUN
Thermal resistor (4-
Yes
wire connection)
Pt 100 standard
range
Thermal resistor (4-
Yes
wire connection)
Pt 100 standard
range
Thermal resistor (4-
Yes
wire connection)
Pt 100 standard
range
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
Scope with configuration
software, e.g., STEP 7 (TIA
Portal)
GSD file
GSD file
PROFINET
PROFIBUS
IO
DP
Channel
Channel
Channel
Channel
Channel
Channel
Manual, 09/2018, A5E03573289-AE