Siemens SIMATIC ET 200SP Manual page 47

Analog input module
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Technical specifications
6.1 Technical specifications
Article number
Supply voltage
Rated value (DC)
permissible range, lower limit (DC)
permissible range, upper limit (DC)
Reverse polarity protection
Input current
Current consumption, max.
Power loss
Power loss, typ.
Address area
Address space per module
Address space per module, max.
Analog inputs
Number of analog inputs
For voltage measurement
For resistance/resistance thermometer
measurement
For thermocouple measurement
permissible input voltage for voltage input
(destruction limit), max.
Constant measurement current for resistance-
type transmitter, typ.
Cycle time (all channels), min.
Technical unit for temperature measurement
adjustable
Input ranges (rated values), voltages
-1 V to +1 V
Input resistance (-1 V to +1 V)
-250 mV to +250 mV
Input resistance (-250 mV to +250 mV)
-50 mV to +50 mV
Input resistance (-50 mV to +50 mV)
-80 mV to +80 mV
Input resistance (-80 mV to +80 mV)
46
6ES7134-6JD00-0CA1
24 V
19.2 V
28.8 V
Yes
35 mA
0.75 W
8 byte; + 1 byte for QI information
4
4
4
4
30 V
0.7 mA; 1.7 mA for Cu10 sensors
Sum of the basic conversion times and additional
processing times (depending on the parameteri-
zation of the active channels); for line compensa-
tion in case of a three-wire connection, an
additional cycle is necessary
Yes; °C/°F/K
Yes; 16 bit incl. sign
1 MΩ
Yes; 16 bit incl. sign
1 MΩ
Yes; 16 bit incl. sign
1 MΩ
Yes; 16 bit incl. sign
1 MΩ
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
Manual, 09/2018, A5E03573289-AE

Hide quick links:

Advertisement

Table of Contents
loading