Parameter Settings - Trane SmartGen HSC940 Owner's Manual

Table of Contents

Advertisement

Start the controller, then press
Fig. 1
Parameters Setting
When entering password interface, input correct password (default: 1234) can set all of the parameter items in
Form 1. If there is need to set more parameters (e.g. Voltage Calibration), please contact the factory.
CAUTION: Please change the controller parameters when generator is in standby mode only
(e. g. Crank disconnect conditions selection, auxiliary input, auxiliary output, various delay),
otherwise, shutdown and other abnormal conditions may happen.
CAUTION: Over voltage set value must be higher than under voltage set value, otherwise
over voltage and under voltage condition may occur simultaneously.
CAUTION: Over speed set value must be higher than under speed set value, otherwise over
speed and under speed condition may occur simultaneously.
CAUTION: Please set the generator frequency value as low as possible when cranking, in
order to make the starter be separated quickly as soon as possible.
CAUTION: Auxiliary input 1~5 could not be set as same items; otherwise, there are abnormal
functions. However, the auxiliary output 1~4 can be set as same items.
CAUTION: If need to shut down after cooling, please set any digital input as "WTH STOP by
cool", then connect this input port to ground soundly.
Information
LCD will display software version, issue date of the controller.
Note: In this interface, pressing
Language
Chinese, English, Spanish and Russian interface can be selected.
Time and Date
The time and date information can be set in this interface.
Pressing the
key at any time will quit the setting and return to the previous settings menu.
032-5094-1A-EN

Parameter Settings

to enter into the parameters setting menu, see fig 1 below:
1. Set Parameters
2. Information
3. Language
4. Time and Date
will display the auxiliary inputs and outputs status.
23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents