Settings For Co 2 -Based Demand Controlled Ventilation - Trane Tracer UC400 Installation, Operation And Maintenance Manual

Programmable controllers for blower coil, fan coil, and unit ventilator
Table of Contents

Advertisement

Settings for CO
The CO
the ASHRAE Standard 62.1 User Manual, Appendix A.
N N o o t t e e : : This sequence is intended for a fan-coil, blower-coil, and unit ventilator product that is
The following describes how to determine the appropriate OA damper and CO
DCV sequence:
BAS-SVX48H-EN
-Based Demand Controlled Ventilation
2
-based DCV sequence used in UC400 Controller is based on the sequence suggested in
2
applied as a single-zone ventilation system. That is to say, outdoor air enters through an
intake and is delivered to a single ventilation zone, which would be typical of a terminal
unit that is equipped with its own OA damper.
Calculate the required outdoor airflow (V
2- and 6-3 from ASHRAE Standard 62.1
V
= R
× P
+ R
× A
(Equation 6-1)
bz
p
z
a
z
V
= V
/ E
(Equation 6-2)
oz
bz
z
V
= V
(Equation 6-3, for single-zone ventilation systems), where
ot
oz
V
= minimum outdoor airflow required in the breathing zone, cfm
bz
R
= outdoor airflow required per person (from Table 6-1 in ASHRAE Standard 62.1), cfm/
p
person
R
= outdoor airflow required per unit of floor area (from Table 6-1 in ASHRAE Standard 62.1),
a
cfm/ft2
P
= zone population, number of people
z
A
= zone floor area, ft
2
z
V
= zone outdoor airflow required, cfm
oz
E
= zone air distribution effectiveness (from Table 6-2 in ASHRAE Standard 62.1)
z
V
= outdoor air intake flow required, cfm
ot
E E x x a a m m p p l l e e : : Consider an example K-12 classroom with a design population (P
and a floor area (A
) of 1000 ft2. Table 6-1 in ASHRAE Standard 62.1-2010 requires 10 cfm of
z
outdoor air per person (R
this type of space. The zone air-distribution effectiveness (from Table 6-2in Standard 62.1) is
determined to be 1.0 for this system configuration.
V
= 10 cfm/p x 35 people + 0.12 cfm/ft
bz-Design
V
= 470 cfm / 1.0 = 470 cfm
oz-Design
V
= 470 cfm
ot-Design
Use the same equations to calculate the required outdoor airflow (V
are currently present in the zone (P
N N o o t t e e : : This setpoint may need to be increased if the zone requires makeup air to replace air
that is exhausted directly from the zone (for example in a kitchen, a laboratory, an art
or science classroom, or any space with a restroom connected to it). In this case, the
V
setpoint may need to be adjusted so that it is slightly above the local exhaust
ot-DCVmin
airflow to ensure positive building pressurization.
E E x x a a m m p p l l e e : :
V
= 10 cfm/p x 0 people + 0.12 cfm/ft
bz-DCVmin
V
= 120 cfm / 1.0 = 120 cfm
oz-DCVmin
V
= 120 cfm
ot-DCVmin
Use Equation A-J from the ASHRAE Standard 62.1-2010 User's Manual to calculate the
steady-state indoor CO
2
its design outdoor airflow rate (V
CO
= CO
+ [1,000,000 x N / (V
2space
2outdoors
CO
= concentration of CO
2space
) at design occupancy using Equations 6-1, 6-
ot-Design
) plus 0.12 cfm of outdoor air per square foot of floor area (R
p
2
x 1000 ft
= 0).
z
2
x 1000 ft
concentration (CO
2
space-Design
).
bz-Design
/ P
)] (rearrangement of Equation A-J) where,
bz
z
in the breathing zone, ppm
2
setpoints for this
2
) of 35 people
z
2
= 470 cfm
) if no occupants
ot-DCVmin
2
= 120 cfm
) when the zone is fully occupied and at
) for
a
63

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tracer uc400-b

Table of Contents