Ethernet Receiver 1 Options - DSC GS2060-SM Installation Manual

Alarm communicator, gprs cellular communicator, ethernet/internet communicator, ethernet/internet and gprs dual-path communicator
Table of Contents

Advertisement

Alternate Test Transmission:
Alternate Test Transmission can be enabled or disabled in Section [005] Toggle Option [7].
[026] Ethernet 1 Transmission
Default (FF)
Program 00 to disable this event transmission or FF to enable. See System Test Options (above) for details on settings.
[027] Ethernet 2 Transmission
Default (00)
Program 00 to disable this event transmission or FF to enable. See System Test Options (above) for details on settings.
[028] GPRS 1 Transmission
Default (FF)
Program 00 to disable this event transmission or FF to enable. See System Test Options (above) for details on settings.
[029] GPRS 2 Transmission
Default (00)
Program 00 to disable this event transmission or FF to enable. See System Test Options (above) for details on settings.
NOTE: The time interval (in minutes) between periodic tests is programmed in Section [125] (Ethernet)
and Section [225] (GPRS).
[030] FTC Restore
Default (FF)
Program 00 to disable this event transmission or FF to enable. This event will occur when an FTC Trouble on the
system restores.
[031] Panel Tamper Alarm
Default (FF)
This event will occur when a Panel Tamper is detected during the Entry Delay time. The Panel shall notify the
Communicator immediately, creating a Priority Tamper Alarm condition. Setting this option to 00 will disable
monitoring of this condition. See Table 9 for SIA and CID reporting codes. Program 00 to disable this event
transmission or FF to enable event transmission.
Event
[031] Panel Tamper
[032] Panel Tamper Restore
[032] Panel Tamper Alarm Restore
Default (FF)
Program 00 to disable this event transmission or FF to enable. This event will occur when a Panel Tamper event on
the system restores. See Table 9 for SIA and CID reporting codes.

Ethernet Receiver 1 Options

[101] Ethernet Receiver 1 Account Code
Default (0000000000)
The account code is used by the central station to distinguish between transmitters. This account code is used
when transmitting heartbeat signals to the central station receiver. Signals received from the Panel will use the con-
trol panel account number. Valid range: 0000000001-FFFFFFFFFE.
Programming this Section as all 0 or all F will cause a Module Configuration Trouble (yellow LED=12 flashes).
NOTE: If Ethernet Receiver 1 and GPRS Receiver 1 are programmed as the same receiver (IP and port
number are identical), Ethernet Receiver 1 account code will be used.
[102] Ethernet Receiver 1 DNIS
Default (000000)
The Dialled Number Information Service (DNIS) is used in addition to the Account Code to identify the Communica-
tor module at the central station. Valid range: 000000 - 099999. Value is entered as a leading 0 followed by the 5
digit DNIS. Format is Binary Coded Decimal (BCD.
NOTE: Each Ethernet/GPRS receiver must be programmed with a unique DNIS.
[103] Ethernet Receiver 1 Address
Default (127.000.000.001)
The default address enables the Communicator to operate in Unattended Mode.
Unattended Mode is used when a receiver is not available and the unit is required to perform DLS sessions. Typi-
cally used where the customer programs the control panel daily due to access control and still wants to receive
alarms without buying extra hardware (receiver) or software.
NOTE: When a valid IP address has been programmed, Ethernet Receiver 1 is enabled and will commu-
nicate events over the Ethernet channel.
Ethernet Receiver 1 and GPRS Receiver 1 may be configured to communicate to the same central station receiver.
To configure the device to operate using this Common Receiver Mode functionality, program Ethernet Receiver 1
and GPRS Receiver 1, IP address and port number with identical values.
NOTE: When operating in Common Receiver Mode, Ethernet Receiver 1 account code will be used for
Ethernet and GPRS.
[104] Ethernet Receiver 1 Remote Port
Default (0BF5/3061)
This Section determines the remote port of Ethernet receiver 1. Valid range: 0000 - FFFF.
SIA
SIA
Reporting
Identifier
Code
ES
001
EJ
001
19
Table 9: Panel Tamper Reporting Codes
CID
CID
Event
Qualifier
Code
1
1
3
1
CID
CID
Reporting
User/
Code
Zone
45
001
45
001