Frequency Setting - Remote Control

The inverter's remote control is operational when the inverter is in the remote control
mode. The "PANEL CONTROL" LED is off. All frequency setting input signals (0-5Vdc,
0-10Vdc, 0-20mA, 4-20mA, 3k ohm pot, JOG, and Preset Speeds) are applied to the
drive through the terminal block which is located on the control/driver printed wiring board
(see page 4-11 for terminal block and jumper details).
8.4.1

Proportional/Follower Input Signals

The following table illustrates the connections required for receiving the different
analog input signals.
Terminal/Jumper Connections for Input Reference Signals
JP1
I
V
10V
1
I
V
10V
2
I
V
10V
3
N/A
I
V
10V
4
I
V
10V
5
N/A
I
V
10V
6
N/A
I
V
10V
6*
JP2
Terminal Connections
5V
NO CONNECTIONS, JP1 & JP2 should be
set as shown for normal panel operation.
PP
5V
+
5V
PP
+
PP
5V
5V
PP
0~5Vdc
PP
5V
0~20mA
(4~20mA)
PP
5V
SW
8 - 12
Required for normal panel operation.
Required for standard 0~5Vdc input
RR
IV
CC
reference signal. Function No. 5
RR terminal priority should be set to
0~5Vdc
_
1 "on" when using this feature.
See Ref. page 8-23.
Required for standard 0~10Vdc input
RR
IV
CC
reference signal. Function No. 5
RR terminal priority should be set to
0~10Vdc
1 "on" when using this feature.
_
See Ref. page 8-23.
RR
IV
CC
Required when using a 3k ohm pot.
A 1K to 10K ohm pot can also be
3k ohm
used but the pot adjustments will be
more critical.
Required for standard 0~5Vdc input
RR
IV
CC
reference signal. Function No. 5
RR terminal priority should be set to
the normal setting of 0 "off" when
inputting a signal to the IV terminal.
See Ref. page 8-23.
Required for standard 0~20mA,
RR
IV
CC
4~20mA input reference signal.
Function No. 5 RR terminal priority
should be set to the normal setting
of 0 "off" when inputting a signal to
the IV terminal. See Ref. page 8-23.
When switch is closed (ON), the
RR
IV
CC
remote pot will override the
0~20/4~20mA input reference
0~20mA
signal. Function No. 5 RR terminal
(4~20mA)
priority should be set to the normal
setting of 0 "off".