Toshiba TOSVERT-130G2+ Operation Manual page 12

High performance transistor inverter igbt digital series
Table of Contents

Advertisement

3.0
Standard Specifications
MODEL
RATED
MOTOR
KVA
HP/KW
*G2+2010
1
0.75/0.9
*G2+2015
1.5
1/1.2
*G2+2025
2.5
2/1.8
*G2+2035
3.5
3/2.5
*G2+2055
5.5
5/4.0
*G2+2080
8
7.5/5.5
*G2+2110
11
10/7.5
*G2+2160
16
15/11
*G2+2220
22
20/15
*G2+2270
27
25/18
*G2+2330
33
30/23
*G2+4015
1.5
1/0.75
*G2+4025
2.5
2/1.5
*G2+4035
3.5
3/2.2
*G2+4055
5.5
5/3.7
*G2+4080
8
7.5/5.5
*G2+4110
11
10/7.5
*G2+4160
16
15/11
*G2+4220
22
20/15
*G2+4270
27
25/18.5
*G2+4330
33
30/22
*G2+4400
40
40/30
*G2+4500
50
50/37
*G2+4600
60
60/45
*G2+4750
75
75/55
*G2+410K
100
100/75
*G2+412K
125
125/90
*G2+415K
150
150/110
*G2+420K
200
200/150
*G2+425K
250
250/200
**G2+430K
300
300/225
*
These units are UL/CUL (Underwriters Laboratories Inc.) listed and CSA (Canadian Standards
Association) certified.
**
Unit is UL/CUL listed only.
RATING
OUTPUT
OUTPUT
CURRENT
VOLTAGE
AMPS
3.5
200-230V
5
3-PHASE
7
(MAX VOLTAGE
10
UNDER NO LOAD)
16
22
30
45
60
70
90
2.7
400-460V
3.5
3-PHASE
5
(MAX VOLTAGE
8
UNDER NO LOAD)
11
15
380-460V
22
3-PHASE
30
MAX VOLTAGE
38
UNDER NO LOAD)
45
55
69
83
104
138
172
206
275
343
415
3 - 1
INPUT POWER (Volt/Freq)
OVERLOAD
MAIN CIRCUIT
CURRENT
3-PHASE
150% FOR
200V/50Hz or
120 SEC.
200-230V/60Hz
110%
VOLTAGE +/- 10%
CONTINUOUS
FREQUENCY +/- 2Hz
400V/50Hz or
400-460V/60Hz
VOLTAGE +/- 10%
FREQUENCY +/- 2Hz
380V/50Hz or
400-460V/60Hz
VOLTAGE +/- 10%
FREQUENCY +/- 2Hz
130% FOR
195 SEC.
110%
CONTINUOUS
TOSHIBA
CONTROL
CIRCUIT SINGLE
PHASE
NO EXTERNAL
CONTROL
SOURCE
REQUIRED