The Output Groups tab allows you to configure the following:
A group of horns to sound for a set time during a set period
Energize or de-energize a group of doors during a set period
In the Output Groups tab, you can configure the following for one or more groups:
Pulse time
Disable/Enable Latch
Energized (schedule selection)
Disable Interlock (schedule selection)
1.
Navigate to the Output Groups tab: Click Panel Configuration > Outputs > Groups.
Figure 2-30 Configuring Output Groups
2.
Click to
add a new group.
3.
Configure the following for each output group:
Setting
Name
Pulse Time
Latch
Energized
Disable Interlocks
4.
Click toggle(s) to select outputs. Click the Choose Outputs toggle to select all
outputs.
5.
Click Save.
Description
Enter a unique name for the group
Configure how long a device assumes abnormal status, such
as a horn sounding or a released door strike. In
hours:minutes:seconds. Maximum time is 1:45:59.
Toggles the state of the outputs between energized and
de-energized status upon every activation (code use, interlock,
or manual pulse).
Specifies the period during which the group of output relays
are automatically energized. Select a schedule (that you
created in
Entering a Panel Name on page
drop-down list.
Specifies the period during which the interlocks that control
the group's outputs will be disabled. Select a schedule (that
you created in
Entering a Panel Name on page
drop-down list.