Siemens CP-8000 User Manual page 386

Sicam a8000 series
Hide thumbs Also See for CP-8000:
Table of Contents

Advertisement

Engineering via SICAM WEB
Processing type
DO_SI – digital output –
single-point information
DO_SX – single-point
information and single
command output
386
Unrestricted
Parameter
RS_Mon_Source
Sw_Seq_command_seq
Sw_Seq_addtl_com
SID-BSE
SID-ST
SID-SSE
QOC>8
RS_Image
receive_format
Fail_behav
SID-BSE
SID-ST
SID-SSE
receive_format
Fail_behav
SID-BSE
SID-ST
SID-SSE
select_execute_t
RS_Image_CASDU1
RS_Image_CASDU2
RS_Image_IOA1
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
Meaning
Source of state information for state infor-
mation monitoring
· Peripherals
· Open-/closed loop control function
· Both (logical OR)
Switching sequence: output additional com-
mand before or after the command
Switching sequence: Select the additional
command
Source identification basic system element
Source identification station number if mul-
tipoint traffic mode 0...99 if R-SID 0...254; if
automatic, the SID will be learned
Source identification supplementary system
element
If QOC > 8 (Qualifier of Command) is accept-
ed, so all QOC > 8 will be interpreted as
QOC = 0
Parameter works only with ACP 1703 platform
Source of datapoint
Behavior at failure
Source identification basic system element
Source identification station number if mul-
tipoint traffic mode 0...99 if R-SID 0...254; if
automatic, the SID will be learned
Source identification supplementary system
element
Source of datapoint
Behavior at failure
· Keep
· Terminate
Source identification basic system element
Source identification station number if mul-
tipoint traffic mode 0...99 if R-SID 0...254; if
automatic, the SID will be learned
Source identification supplementary system
element
Max. time between select and execute (in
seconds). After this time a recent select com-
mand is necessary.
0 = no select command is expected (direct
command transmission)
0 to 6553.5
Address of corresponding return state infor-
mation (S)
0 to 255
Address of corresponding return state infor-
mation (S)
0 to 255
Address of corresponding return state infor-
mation (S)
0 to 255
DC8-037-2.02, Edition 10.2017