Siemens CP-8000 User Manual page 252

Sicam a8000 series
Hide thumbs Also See for CP-8000:
Table of Contents

Advertisement

Preparing the Engineering
With CP-802x, a standard patch cable and a D-sub/RJ45 adapter must be used.
SICAM TOOLBOX II
Wiring for Connection CP-8000 – PC (patch cable + D-sub/RJ45 adapter)
CTS
X2:1
X2:2
RTS
VCC
X2:3
X2:4
TXD
RXD
X2:5
GND
X2:6
DCD
X2:7
X2:8
DTR
shield
Recommended D-sub/RJ45 adapter
RS Pro MHDA9-SMJ8-M-K (see appendix A.8.1,
adapter provides a wired RJ45 socket and an unwired D-sub plug (female).
Wiring of the RJ45 socket:
Pin
Wire color
1
black
2
yellow
3
orange
4
red
5
green
6
browne
7
grey
8
blue
Shield
black
Note
If the engineering PC does not provide a serial COM port, additionally a USB/RS-232 converter is required
(see appendix A.8.1,
252
Unrestricted
Standard patch cable
max. 1.8 m
TOOLBOX II
Revision :
License Pak:
Version 5 | Siemen s AG
D-sub/RJ45
adaptor
1
2
3
4
5
6
7
8
Recommended Third-Party
9-pole D-sub
female
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Recommended Third-Party
Wiring at the 9-pole D-sub plug:
The assignment of the pins at the D-sub plug can be
made according to wiring diagram.
RJ45 socket
Not used wires must be isolated!
With use of the shield this must be soldered at the metal
plate of the D-sub plug.
Products).
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
CP-802x
Engineering
PC
1
DCD
2
RXD
3
TXD
4
DTR
5
GND
6
DSR
7
RTS
8
CTS
9
RI
shield
Products). This
D-sub plug (backside)
.
solding point
DC8-037-2.02, Edition 10.2017