Siemens CP-8000 User Manual page 375

Sicam a8000 series
Hide thumbs Also See for CP-8000:
Table of Contents

Advertisement

Processing type
SW_DI – software data
point digital input
SW_DI_AR - automatic
reclosing
SW_DI_UPDATE –
update of double-point
information
SW_DI_BT – breaker
tripping
SW_DI_SOR – switching
operation running
SW_CV_SET – counter
set
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Parameter
SVM_monitoring
transm_prompting
latch_prompting
Value range
Pulse value
Moduleselection_SVM_
monitoring
Originatoraddress
QOC
SID-BSE
SID-ST
SID-SSE
SID-BSE
SID-ST
SID-SSE
Engineering via SICAM WEB
Meaning
· Latched absolute value
· Latched relative value
Power monitoring. The sensor voltage is
monitored by an own power monitoring input
(S)
Transmission prompting. The initiating for the
transfer of the latched count can happen
through a counter interrogation message
(group), through adjustable intervals, or
through the function diagramm. (S)
Latch prompting can be different to the trans-
mission prompting (S)
Value range of the counter (S)
Pulse value (S)
0.0001 bis 9999
Switch for power monitoring handling (PM)
Standard PM (PM inputs per modules) or input
IN D17 of one BI-module as PM input for all
modules Attention: Selected module must be
a DI-module.
Allowed originator address
there is no confirmation/termination for a
received command with a different QOC
Source identification basic system element
Source identification station number if mul-
tipoint traffic mode 0...99 if R-SID 0...254; if
automatic, the SID will be learned
Source identification supplementary system
element
Source identification basic system element
Source identification station number if mul-
tipoint traffic mode 0...99 if R-SID 0...254; if
automatic, the SID will be learned
Source identification supplementary system
element
Unrestricted
375