Brine Units; Water Treatment; Preparation For Year-Round Operation; Winter Shutdown Preparation - Carrier R080-528 Installation Instructions Manual

Air-cooled chillers, 60 hz
Table of Contents

Advertisement

PIPE SIZE
MODEL
in. (mm)
Flex-Hose SVG8
8 (219)
Unaflex Style 1000
8 (219)
BRINE UNITS — Special factory modifications to the units
are required to allow them to operate at fluid temperatures less
than 34 F (1.1 C). Be sure that the fluid has sufficient inhibited
glycol or other suitable corrosion-resistant antifreeze solution
to prevent cooler freeze-up.
WATER TREATMENT — Fill the fluid loop with water (or
brine) and a corrosion-resistant inhibitor suitable for the water
of the area. Consult the local water treatment specialist for
characteristics of system water and a recommended inhibitor
for the cooler fluid loop. It is recommended that once the
cooler water lines have been installed and leak checked that the
cooler heads be insulated with a suitable thickness of closed-
cell insulation. This will minimize the amount of condensation
that will form on the cooler heads.
PREPARATION FOR YEAR-ROUND OPERATION — In
areas where the piping or unit is exposed to 32 F (0° C) or low-
er ambient temperatures, freeze-up protection is required using
inhibited glycol or other suitable corrosion-resistant antifreeze
solution and electric heater tapes. Heater tapes on piping
should have a rating for area ambient temperatures and be cov-
ered with a suitable thickness of closed-cell insulation. Route
power for the heater tapes from a separately fused disconnect.
Mount the disconnect within sight from the unit per local or
NEC codes. Identify disconnect as heater tape power source
with warning that power must not be turned off except when
servicing unit.
IMPORTANT: Adding antifreeze solution is the only cer-
tain means of protecting the unit from freeze-up if heater
fails or electrical power is interrupted or lost while tempera-
tures are below 32 F (0° C).
IMPORTANT: Before starting the unit, be sure all of the air
has been purged from the system.
A drain connection is located at the bottom of the cooler
head. See Fig. 1-25 and 34 for connection location. Install shut-
off valves to the drain line before filling the system with fluid.
WINTER SHUTDOWN PREPARATION — At the end of
each cooling season the fluid should be drained from the sys-
tem. However, due to the cooler circuiting, some fluid will re-
main in the cooler after draining. To prevent freeze-up damage
to the cooler tubes perform the following procedure.
1. If factory-installed cooler heaters have been installed,
deenergize the heaters to prevent damage and possible
safety hazards when draining, or when there is no liquid
in the system. Remove Fuse 1 to deenergize heaters.
Drain the fluid from the system.
2. Isolate the cooler from the rest of the system with
water shut-off valves.
Table 5 — Flexible Coupling Alignment
MAX. PARALLEL
LENGTH
OFFSET
in. (mm)
in. (mm)
16 (406)
0.5 (13)
6 (152)
1 (25)
MAX.
MAX.
ELONGATION
COMPRESSION
in. (mm)
in. (mm)
0
0
0.75 (19)
1.75 (44)
3. Completely fill the cooler with an appropriate amount
of inhibited glycol solution (or other suitable
corrosion-inhibitive antifreeze) for 15° F (8.3° C)
below the expected low ambient conditions, 5 gallons
(19 L) minimum.
4. Leave the cooler filled with the antifreeze solution for
the winter, or drain if desired. Be sure to deenergize
heaters (if installed) as explained in Step 1 to prevent
damage. Use an approved method of disposal when
removing antifreeze solution.
Fig. 29 — Victaulic Flange
COUPLING
Fig. 30 — Flow Sensor Coupling, Victaulic Flange
NOZZLE CONNECTIONS
Fig. 31 — Victaulic Flange Connection Locations
45
MAX. WORKING
CONNECTION
PRESSURE
STYLE
PSI
Victaulic/Varies
155
Flange
150

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecologic 30gxn

Table of Contents