Carrier R080-528 Installation Instructions Manual page 62

Air-cooled chillers, 60 hz
Table of Contents

Advertisement

Table 7D — Electrical Data High Ambient 125 F Data, High-Static Condenser Fan (cont)
UNIT VOLTAGE
UNIT
Supplied
V-Hz
30GXN,R
(3 Ph)
Min
Max
208/230-60
187
253
230-60
207
253
460-60
414
506
228
575-60
518
633
380-60
342
418
208/230-60
187
253
230-60
207
253
249
460-60
414
506
575-60
518
633
380-60
342
418
208/230-60
187
253
230-60
207
253
253
460-60
414
506
575-60
518
633
380-60
342
418
208/230-60
187
253
230-60
207
253
264
460-60
414
506
575-60
518
633
380-60
342
418
208/230-60
187
253
230-60
207
253
460-60
414
506
268
575-60
518
633
380-60
342
418
460-60
414
506
281
575-60
518
633
380-60
342
418
460-60
414
506
301
575-60
518
633
380-60
342
418
460-60
414
506
325
575-60
518
633
380-60
342
418
460-60
414
506
350
575-60
518
633
380-60
342
418
LEGEND
ICF
— Maximum Instantaneous Current Flow
MCA
— Minimum Circuit Ampacity (for wire sizing)
MOCP
— Maximum Overcurrent Protection
Rec Fuse Size — Recommended Dual-Element Fuse Amps (150% of largest
compressor rated load amps [RLA] plus 100% of remaining
compressor RLAs and sum of condenser fan full load amps
[FLAs]. Choose next largest standard fuse size.)
WD
— Wye-Delta Start
XL
— Across-the-Line Start
*Amperages in ( ) are for units with cooler heaters installed.
†Wye-delta start is standard. Across-the-line start is not available.
**Circuit A/Circuit B.
NOTES:
1. Main power must be supplied from a field-supplied fused electrical service with a
(factory or field-installed) disconnect located in sight from the unit.
2. Cooler heater, oil heater, and control circuit power must be supplied from a separate
source through a field-supplied disconnect. The control circuit power transformer acces-
sory may be applied to power from the main unit power supply.
3. Maximum incoming wire size for each terminal block is 500 kcmil.
4. Maximum allowable supply voltage phase imbalance is voltage 2%.
5. Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percent voltage imbalance.
Percent Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 240-3-60.
AB = 243 v
BC = 236 v
AC = 238 v
Average voltage =
=
POWER
SUPPLY
# Power Supply
MCA
QTY. REQD
Conductors
2
12
693/488**
2
12
627/461**
1
6
504
1
6
406
1
6
607
2
12
753/518**
2
12
681/486**
1
6
540
1
6
433
1
6
651
2
12
752/577**
2
12
681/545**
1
6
566
1
6
455
1
6
681
2
12
753/594**
2
12
681/553**
1
6
567
1
6
454
1
6
685
2
12
752/652**
2
12
681/612**
1
6
593
1
6
477
1
6
713
1
6
613
1
6
493
1
6
741
1
6
646
1
6
519
2
9
354/472**
1
6
539
1
6
432
2
9
379/498**
1
6
744
1
6
596
2
12
413/531**
243 + 236 + 238
3
239 v
HIGH-STATIC CONDENSER FAN
ICF
MOCP
XL
WD
1000/700**
1017.9/722.4**
800/600**
991.8/722.4**
600
1490.2
686.2
500
1194.4
551.4
700
1677.3
788.3
1000/700**
1077.7/756.2**
800/700**
1045.6/756.2**
600
1526.3
722.3
500
1221.8
578.8
800
1721.2
832.2
1000/800**
1077.4/814.6**
800/700**
1045.6/814.6**
700
1551.5
747.5
500
1243.8
600.8
800
1751.0
862.0
1000/800**
1077.7/918.2**
800/800**
1045.6/918.2**
700
1553.2
749.2
500
1243.6
600.6
800
1754.6
865.6
1000/800**
1077.4/814.6**
800/800**
1045.6/814.6**
700
1578.4
774.4
500
1265.3
622.3
800
1783.5
894.5
700
1598.9
794.9
600
1282.4
639.4
800
1811.2
922.2
700
1632.3
828.3
600
1308.0
665.0
500/600**
1423.4/1541.8**
534.4/652.8**
600
1675.9
871.9
500
1341.4
698.4
500/600**
1449.0/1567.4**
560.0/678.4**
800
1729.7
925.7
700
1385.0
742.0
500/700**
1482.4/1600.8**
593.4/711.8**
Determine maximum deviation from average voltage:
(AB) 243 – 239 = 4 v
(BC) 239 – 236 = 3 v
(AC) 239 – 238 = 1 v
Maximum deviation is 4 v. Determine percent voltage imbalance:
% Voltage Imbalance
= 100 x
= 1.7%
This amount of phase imbalance is satisfactory as it is below the maximum allow-
able 2%.
IMPORTANT: Contact your local electric utility company immediately if the supply
voltage phase imbalance is more than 2%.
62
CONTROL CIRCUIT
Rec Fuse Size
V-Hz
MCA and
(Single Ph)
XL
WD
800/600**
115-60
800/600**
115-60
600
600
115-60
450
450
115-60
700
700
230-60
1000/600**
115-60
800/600**
115-60
600
600
115-60
500
500
115-60
700
700
230-60
1000/700**
115-60
800/700**
115-60
700
700
115-60
500
500
115-60
800
800
230-60
1000/700**
115-60
800/700**
115-60
700
700
115-60
500
500
115-60
800
800
230-60
1000/700**
115-60
800/700**
115-60
700
700
115-60
600
600
115-60
800
800
230-60
700
700
115-60
600
600
115-60
800
800
230-60
700
700
115-60
600
600
115-60
400/600**
400/600**
230-60
600
600
115-60
500
500
115-60
450/600**
450/600**
230-60
800
800
115-60
700
700
115-60
500/600**
500/600**
230-60
4
239
MOCP*
30 (50)
30 (50)
30 (50)
30 (50)
15 (25)
30 (50)
30 (50)
30 (50)
30 (50)
15 (25)
30 (50)
30 (50)
30 (50)
30 (50)
15 (25)
30 (50)
30 (50)
30 (50)
30 (50)
15 (25)
30 (50)
30 (50)
30 (50)
30 (50)
15 (25)
30 (50)
30 (50)
15 (25)
30 (50)
30 (50)
15 (25)
30 (50)
30 (50)
15 (25)
30 (50)
30 (50)
15 (25)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecologic 30gxn

Table of Contents