Carrier R080-528 Installation Instructions Manual page 57

Air-cooled chillers, 60 hz
Table of Contents

Advertisement

Table 7A — Electrical Data Reduced Ambient 115 F Data (cont)
UNIT VOLTAGE
UNIT
Supplied
V-Hz
30GXN,R
(3 Ph)
Min
208/230-60
187
230-60
207
128
460-60
414
575-60
518
380-60
342
208/230-60
187
138,
230-60
207
283B, 303B,
460-60
414
373B
575-60
518
380-60
342
208/230-60
187
153,
230-60
207
283A, 328B,
460-60
414
393B, 418B
575-60
518
380-60
342
208/230-60
187
230-60
207
163,
460-60
414
303A
575-60
518
380-60
342
208/230-60
187
230-60
207
178,
460-60
414
328A, 353A/B
575-60
518
380-60
342
208/230-60
187
230-60
207
208
460-60
414
575-60
518
380-60
342
208/230-60
187
230-60
207
228,
460-60
414
453A/B, 478B
575-60
518
380-60
342
208/230-60
187
253,
230-60
207
373A, 393A,
460-60
414
478A, 503A/B
575-60
518
380-60
342
208/230-60
187
230-60
207
268,
460-60
414
418A, 528A/B
575-60
518
380-60
342
LEGEND
ICF
— Maximum Instantaneous Current Flow
MCA
— Minimum Circuit Ampacity (for wire sizing)
— Maximum Overcurrent Protection
MOCP
Rec Fuse Size — Recommended Dual-Element Fuse Amps (150% of largest
compressor rated load amps [RLA] plus 100% of remaining
compressor RLAs and sum of condenser fan full load amps
[FLAs]. Choose next largest standard fuse size.)
WD
— Wye-Delta Start
XL
— Across-the-Line Start
*Wye-delta start is standard. Across-the-line start is not available.
NOTES:
1. Main power must be supplied from a field-supplied fused electrical service with a
(factory or field-installed) disconnect located in sight from the unit.
2. Cooler heater, oil heater, and control circuit power must be supplied from a separate
source through a field-supplied disconnect. The control circuit power transformer acces-
sory may be applied to power from the main unit power supply.
3. Maximum incoming wire size for each terminal block is 500 kcmil.
4. Maximum allowable supply voltage phase imbalance is voltage 2%.
5. Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percent voltage imbalance.
Percent Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 240-3-60.
AB = 243 v
BC = 236 v
AC = 238 v
Average voltage =
=
POWER
# Power
SUPPLY
Supply
QTY. REQD
Max
Conductors
253
1
6
253
1
6
506
1
3
633
1
3
418
1
3
253
1
6
253
1
6
506
1
3
633
1
3
418
1
3
253
2
9
253
1
6
506
1
3
633
1
3
418
1
6
253
2
9
253
2
9
506
1
3
633
1
3
418
1
6
253
2
9
253
2
9
506
1
6
633
1
3
418
1
6
253
2
12
253
2
12
506
1
6
633
1
3
418
1
6
253
2
12
253
2
12
506
1
6
633
1
3
418
1
6
253
2
12
253
2
12
506
1
6
633
1
6
418
1
6
253
2
12
253
2
12
506
1
6
633
1
6
418
1
6
243 + 236 + 238
3
239 v
HIGH-STATIC CONDENSER FAN
ICF
MCA
MOCP
XL
584.4
800
*
540.0
700
*
262.0
350
1046.1
210.9
250
838.2
315.2
400
1167.8
623.9
800
*
575.8
700
*
279.9
350
1064.0
225.2
300
852.5
336.9
450
1189.5
524.5/259
800/450
*
889.0/518.0
675.7
800
*
1076.2
327.9
450
1331.6
263.9
350
1066.9
394.5
500
1486.3
553.7/300
800/500
*
918.2/581.0
517.7/272
700/450
*
918.2/581.0
355.6
450
1359.3
286.4
350
1089.4
427.5
500
1519.3
553.7/378
800/600
*
918.2/743.0
517.7/343
700/600
*
918.2/743.0
383.9
500
1387.6
309.0
400
1112.0
461.8
600
1553.6
541/463
700/600
*
821.2/722.4
489/443
700/600
*
798.4/705.2
426
500
1210.5
343
400
970.6
513
600
1365.4
619/463
800/600
*
983.2/722.4
560/443
800/600
*
960.4/705.2
462
500
1465.5
372
450
1174.6
556
700
1647.4
681/534
800/700
*
1045.8/814.6
617/509
800/700
*
1017.0/798.4
518
600
1521.5
417
500
1219.8
623
700
1714.7
681/612
800/800
*
1045.8/976.6
617/576
800/800
*
1017.0/976.6
546
600
1549.8
439
500
1242.4
657
800
1748.9
Determine maximum deviation from average voltage:
(AB) 243 – 239 = 4 v
(BC) 239 – 236 = 3 v
(AC) 239 – 238 = 1 v
Maximum deviation is 4 v. Determine percent voltage imbalance:
% Voltage Imbalance
This amount of phase imbalance is satisfactory as it is below the maximum allow-
able 2%.
IMPORTANT: Contact your local electric utility company immediately if the supply
voltage phase imbalance is more than 2%.
57
CONTROL CIRCUIT
Rec Fuse Size
V-Hz
(Single Ph)
WD
XL
WD
865.1
*
700
115-60
849.2
*
600
115-60
417.1
300
300
115-60
335.2
250
250
115-60
471.8
350
350
230-60
904.7
*
700
115-60
885.0
*
700
115-60
435.0
350
350
115-60
349.5
250
250
115-60
493.5
400
400
230-60
*
700/350
115-60
*
800
115-60
527.6
400
400
115-60
423.9
300
300
115-60
597.3
450
450
230-60
*
700/400
115-60
*
600/350
115-60
555.3
400
400
115-60
446.4
350
350
115-60
630.3
500
500
230-60
*
700/500
115-60
*
600/450
115-60
583.6
450
450
115-60
469.0
350
350
115-60
664.6
600
600
230-60
*
700/600
115-60
*
600/500
115-60
581.5
500
500
115-60
467.6
400
400
115-60
669.4
600
600
230-60
*
700/600
115-60
*
700/500
115-60
661.5
500
500
115-60
531.6
400
400
115-60
758.4
600
600
230-60
*
800/600
115-60
*
700/600
115-60
717.5
600
600
115-60
576.8
450
450
115-60
825.7
700
700
230-60
*
800/700
115-60
*
700/700
115-60
745.8
600
600
115-60
599.4
500
500
115-60
859.9
700
700
230-60
4
= 100 x
239
= 1.7%
MCA and
MOCP
30
30
30
30
15
30
30
30
30
15
30
30
30
30
15
30
30
30
30
15
30
30
30
30
15
30 (50)
30 (50)
30 (50)
30 (50)
15 (25)
30 (50)
30 (50)
30 (50)
30 (50)
15 (25)
30 (50)
30 (50)
30 (50)
30 (50)
15 (25)
30 (50)
30 (50)
30 (50)
30 (50)
15 (25)