Mixing Valve
Installation of mixing valve
Balancing Vessel
(Mixing tank)
When two different zones are used with different temperature, adjust the temperature of discharge water to high temperature
water and control the amount of bypass to provide low temperature water by applying the mixing valve and temperature sensor
of the mixing valve (TW4).
1 Select a mixing valve from the manufacturers as below (recommended) and install it at the entrance of the zone.
2 Install the supplied temperature sensor (TW4) on the rear part of the mixing valve. Install TW4 Sensor within 1m of Mixing
Valve.
3 Since running time varies depending on the manufacturer, set the FSV (default 90 sec.) by referring to the FSV value below.
Maker
Model code
Running time
FSV(#4046) setting
NOTE
• The table above is for your reference. It can be changed without advanced notice.
3 Way Valve
R3020-6P3-S2
Actuator
Radiator
TW4
BELIMO
SIEMENS
VXP45.20-4 (kvs 4)
LR230A(-S)
SSB31
90 sec.
150 sec.
9
Under Floor
HONEYWELL
V5011E1213
ML6420A3015
60 sec.
15
6