Maintenance / Repair; Status Query; Performance Check - Siemens FDOOT271 Technical Manual

Radio fire detector
Hide thumbs Also See for FDOOT271:
Table of Contents

Advertisement

7 Maintenance / Repair

7.1 Status query

7.2 Performance check

Building Technologies
Fire Safety
Check the detector on a regular basis, but at least once a year.
To do this, look for/check the following and resolve any problems you identify:
Mechanical damage
l
Soiling
l
Correct fastening
l
Detector function by means of test activation
l
The query is issued from the control panel, via the radio gateway.
The following queries may be issued:
Danger level
l
Detector fault
l
Radio status
l
Depending on the authorization level of the user and the control panel type, the
following actions can be performed:
Device test (Go/No Go or detailed by status polling)
l
Activation of a test alarm
l
Reading out the identification number, customer text and measure text
l
Localizing and setting the parameters of the detector
l
Switching off the detector
l
See also
2 Diagnosis levels [➙ 20]
2 Internal alarm indicator [➙ 20]
The selftest automatically subjects the detectors to an extensive electrical
performance check. Regular performance checks of the detectors are required
nonetheless. These can be performed using test gas or hot air.
Recommendation:
Perform a visual inspection on all detectors every year. Detectors that are
l
heavily soiled or mechanically damaged must be replaced.
All detectors should be replaced after 6 to 8 years of service, depending on the
l
ambient conditions.
Maintenance / Repair
7
Status query
A6V10227635_g_en_--
2015-03-11
43