Specifications

Technical data

8.1 Technical data
Device characteristics
Radio
Battery pack BAT3.6-10
Ambient conditions
Mechanical data
Standards
50
Building Technologies
Fire Safety
You will find information on approvals, CE marking, and the relevant EU directives
for this device (these devices) in the following document(s); see 'Applicable
documents' chapter:
Document A6V10271323
l
Response sensitivity
Compensation speed
Detector diagnosis
Sending/receiving aerials
Frequency range
Channel grid
Number of channels
Transmitting power
Range
Lithium battery pack
Battery service life
Service life in 'battery low' operation
Battery voltage monitored
Weight
Operating temperature:
Storage temperature
Air humidity
Protection category (IEC 60529):
Electromagnetic compatibility:
100 kHz...2.5 GHz
Permissible wind speed:
Color
Weight without accessories
European standards
See also
2 Applicable documents [➙ 7]
2.3...12 %/m
≤1/45 voltage increase for detection/h
With SWING tool
Dual band aerial
868...870 MHz SRD band
433...435 MHz
50 kHz
27 in 868-MHz band
20 in 433-MHz band
<10 mW ERP
See document 'A6V10227631'
BAT3.6-10 LI-SOCl2 battery pack 3.6 V,
10 Ah
At least 3 years depending on the ambient
conditions
>3 months
Yes
0,093 kg
-10...+55 °C
-30...+75 °C
≤95 % rel.
IP30
30 V/m
Max. 5 m/s
∼RAL 9010 pure white
0,132 kg
EN 54-11
l
EN 54-25
l
EN 300220-2
l
EN 301489-3
l
EN 60950
l
A6V10227635_g_en_--