7 – Wiring
(continued)
7-8 AC Input/Output Wiring (Parallel UPS – Single Input Source)
Parallel UPS Warnings:
The total input cable length must be equal to the total
output cable length in order to prevent unbalanced load
sharing between two UPS systems under reserve mode
(i.e. Res1 + OP1 = Res2 + OP2; deviation must be <10%).
Parallel configuration only supports 2 UPS systems (1+1
redundancy or capacity). Do not attempt to link more than
two UPS systems via parallel configuration.
The UPS systems must have the same rating and capacity
for parallel UPS installation. Attempting to link
dissimilar UPS systems will damage the UPS systems
and create a serious risk of personal injury and property
damage.
Each UPS must have its Parallel group set to 2 and a
different "Parallel ID" that indicates the UPS systems are
being run in parallel. (See
1
Follow the steps in
Section
in the diagram.
2
Connect the included parallel UPS cable
of each UPS system.
7-9 AC Input/Output Wiring (Parallel UPS – Dual Input Sources)
Parallel UPS Warnings:
The total input cable length must be equal to the total
output cable length in order to prevent unbalanced load
sharing between two UPS systems under reserve mode
(i.e. Res1 + OP1 = Res2 + OP2; deviation must be <10%).
Parallel configuration only supports 2 UPS systems (1+1
redundancy or capacity). Do not attempt to link more than
two UPS systems via parallel configuration.
The UPS systems must have the same rating and capacity
for parallel UPS installation. Attempting to
link dissimilar UPS systems will damage the UPS systems
and create a serious risk of personal injury and property
damage.
Each UPS must have its Parallel group set to 2 and a
different "Parallel ID" that indicates the UPS systems are
being run in parallel. (See
1
Follow the steps in
Section
in the diagram.
2
Connect the included parallel UPS cable
of each UPS system.
Section 10-5-5
for more details.)
7-7, wiring the UPS systems as shown
A
to the parallel port
Section 10-5-5
for more details.)
7-7, wiring the UPS systems as shown
A
to the parallel port
1
B
B
2
1
B
B
2
21
1
2
3
4
5
B
6
A
7
8
9
10
11
12
B
A
13
14