Owner's Manual
SmartOnline
S3MX
®
3-Phase UPS Systems
Models: S3M30KX, S3M40KX, S3M60KX, S3M80KX
Input: 220/230/240V (Ph-N), 380/400/415V (Ph-Ph), 3Ø 4-Wire + PE
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2018 Tripp Lite. All rights reserved.
1

Advertisement

Table of Contents
loading

Summary of Contents for Tripp Lite S3M30KX

  • Page 1 Owner’s Manual SmartOnline S3MX ® 3-Phase UPS Systems Models: S3M30KX, S3M40KX, S3M60KX, S3M80KX Input: 220/230/240V (Ph-N), 380/400/415V (Ph-Ph), 3Ø 4-Wire + PE 1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support Copyright © 2018 Tripp Lite. All rights reserved.
  • Page 2: Table Of Contents

    Table of Contents 1. Introduction 5. Communication 5.1 SNMP Monitoring Slot 2. Important Safety Warnings 5.2 EPO Connector 2.1 UPS Location Warnings 5.3 RS-232 Port 2.2 Equipment Connection Warnings 5.4 USB Port 2.3 Battery Warnings 6. Troubleshooting 2.4 Transportation and Storage 2.5 Preparation 7.
  • Page 3: Introduction

    1. Introduction Tripp Lite’s SmartOnline S3MKX-Series Uninterruptible Power Supply (UPS) is a Voltage and Frequency Independent (VFI) true on-line, double-conversion 3-phase UPS system. This UPS continuously conditions the incoming electrical power supply, eliminating power disturbances that will otherwise damage sensitive electronic devices and minimizing system downtime from power fluctuations and interruptions.
  • Page 4: Important Safety Warnings

    This manual contains important instructions and warnings that should be followed during the installation and maintenance of all Tripp Lite SmartOnline S3MX 3-Phase 30kVA, 40kVA, 60kVA and 80kVA UPS Systems and their batteries. Failure to heed these warnings may affect your warranty.
  • Page 5: Transportation And Storage

    2. Important Safety Warnings 2.4 Transportation and Storage To protect against shock and impact, transport the UPS system only in the original packaging. The UPS must be stored in a room that is dry and ventilated. 2.5 Preparation Condensation may occur if the UPS system is moved directly from a cold to a warm environment. The UPS system must be completely dry before being installed.
  • Page 6: Operation

    2. Important Safety Warnings • When installing the unit, verify that any maintenance bypass panel used is configured correctly before applying power to the unit. • Be sure to place a warning label on all primary power isolators installed remotely from the UPS area and on any external access points between such isolators and the UPS.
  • Page 7: Installation And Setup

    Notify the carrier and dealer immediately if there is any damage or missing parts. Please keep the original packaging in a safe place for future use. Rear Panel View - 30K and 40K Models (See next page for number descriptions.) S3M30KX Rear Panel S3M40KX Rear Panel S3M30KX and S3M40KX Input/Output Terminals...
  • Page 8 3. Installation and Setup Front Panel View - 60K and 80K Models S3M60KX Front View with Door Open S3M80KX Front View with Door Open S3M60KX and S3M80KX Input/Output Terminals RS-232 Communications Port USB Communications Port Emergency Power Off (EPO) Connector Share Current Port for Paralleling Units Parallel Ports for Paralleling Units SNMP Slot for Network Monitoring using (Optional WEBCARDLX)
  • Page 9: Internal Battery Connection

    3. Installation and Setup 3.2 Internal Battery Connection DANGER! LETHAL HIGH VOLTAGE HAZARD! Potentially lethal high voltage exists within the batteries, even when not connected to a UPS system. Battery connection should be performed by qualified service personnel only, following all the precautions listed in this manual and adhering to local electrical codes.
  • Page 10: Single Ups Installation

    ] 2 AWG [34 mm ] 1/0 AWG [54 mm 1/0 AWG [54 mm 2 AWG [34 mm Table 3.2 UPS Input Breakers Model (Agency Number) Breaker Size S3M30KX (AG-030) 63A, 3-Pole S3M40KX (AG-040) 80A, 3-Pole S3M60KX (AG-060) 150A, 3-Pole S3M80KX (AG-080)
  • Page 11 (Designed For) 10/9Ah x 80 100A (Fuse) Notes: • The S3M30KX cable should be able to withstand over 63A current. It is recommended to use 8 AWG (8 mm ) or thicker wire for Phase and 4 AWG (21 mm ) or thicker wire for Neutral for safety and efficiency.
  • Page 12: Ups Installation For Parallel Systems

    Note: The parallel system cannot use a common external battery pack. Doing so will cause permanent damage to the entire system. 8) Refer to the following wiring diagram for parallel installation: UPS 1 UPS 2 Output Input Wiring Diagram of Parallel System (S3M30KX and S3M40KX Models)
  • Page 13: External Battery Connection

    The S3M30KX and S3M40KX UPS models include a robust internal battery system. The S3M60KX and S3M80KX models require external battery packs. External battery packs may be used with the S3M30KX and S3M40KX models to extend runtime. Adding external batteries will increase runtime and require additional recharge time.* The illustrations below show the location of the UPS system’s external battery connector for the 30K and 40K model where the battery...
  • Page 14: Operation

    4. Operation 4.1 Display Button Operation Button Function ON/Enter Button Turn on the UPS: Press and hold for more than 0.5 seconds to turn on the UPS. Enter Button: Press to confirm a selection in the settings menu. OFF/ESC Button Turn off the UPS: Press and hold for more than 0.5 seconds to turn off the UPS.
  • Page 15 4. Operation LCD Panel Mode Operation Info Mute Operation Battery Info Load Info Backup Time Info Setting Input and Battery Output and Battery Voltage Info Voltage Info Battery Info Fault and Load Info Warning Info Display Function Backup time information Indicates the battery discharge time in numbers H: hours, M: minutes, S: seconds Fault and Warning information...
  • Page 16: Audible Alarm

    4. Operation Battery information Indicates the battery capacity by 0-25%, 26-50%, 51-75% and 76-100%. Indicates the battery is not connected. Indicates low battery level and low battery voltage. Input & Battery voltage information Indicates the input voltage, frequency or battery voltage. VAC: Input Voltage, VDC: Battery Voltage, Hz: Input Frequency 4.3 Audible Alarm Description...
  • Page 17: Charging The Batteries

    4. Operation 4.4.3 Connecting Devices to UPS 1) After the UPS has been turned on, devices may be connected and powered on one at a time. The UPS system’s LCD panel will display the total load level. 2) When connecting devices with inductive loads (such as a printer), the in-rush current should be calculated carefully to confirm it meets the capacity of the UPS.
  • Page 18: Parallel Ups Operation

    1.5V, calibrate the voltage by configuring the inverter voltage adjustment (refer to Program Codes 15, 16 and 17, in section 4.7) in the LCD setting. If the voltage difference after calibration remains greater than 1.5V, contact Tripp Lite Technical Support for further assistance.
  • Page 19 4. Operation 4.5.2 Turning On a Parallel System in On-line Mode 1) Turn on the line input breaker of each UPS. When all UPS systems enter Bypass Mode, measure the output voltage between two UPS systems for the same phase to ensure the phase sequence is correct. If these two voltage differences are near zero, then all connections are correct.
  • Page 20: Lcd Panel Abbreviations

    4. Operation 4.6 LCD Panel Abbreviations Abbreviation Display content Meaning Abbreviation Display content Meaning Enable Reserved Disable Neutral line loss Auto Check Battery OP .V Output voltage Normal Mode (not CVCF Parallel, 001 means the Mode) first UPS CVCF Mode The first phase Subtract The second phase...
  • Page 21 4. Operation Programs Available List for Parameter 1: Bypass / CVCF Battery Battery Code Description No Output mode Mode Mode Mode Mode Test Output voltage Output frequency           Voltage range for bypass          ...
  • Page 22 4. Operation 02: Output Frequency Interface Setting 60 Hz, CVCF Mode Parameter 2: Output Frequency Setting the output frequency. You may choose three options in Parameter 2: 50.0 Hz: The output frequency setting is 50.0 Hz. 60.0 Hz: The output frequency setting is 60.0 Hz. ATO: If selected, output frequency will be decided according to the latest normal utility frequency.
  • Page 23 4. Operation 06: Voltage Range for ECO Mode Interface Setting Parameter 2: Low voltage point in ECO Mode. The setting range is from -5% to -10% of the nominal voltage. Parameter 3: High voltage point in ECO Mode. The setting range is from +5% to +10% of the nominal voltage.
  • Page 24 4. Operation 11: Hot Standby Function Setting Interface Setting Parameter 2: HS.H: Indicates hot standby function. Parameter 3: Enable or disable hot standby function. YES: Hot standby function is enabled. The current UPS is set to host the hot standby function and will restart after AC recovery, even without the battery connected.
  • Page 25 4. Operation 15: Inverter-A Voltage Adjustment Interface Setting Parameter 2: Choose Add or Sub to adjust inverter-A voltage.* Parameter 3: The voltage range is 0V to 9.9V. The default value is 0V. * Add or Sub is according to the output voltage that you set. 16: Inverter-B Voltage Adjustment Interface Setting...
  • Page 26: Operating Mode/Status Description

    Note: Once the charger board is extended, all installed charger boards will charge the battery at the maximum power of 4A current. Extension board kits are available for the S3M30KX and S3M40KX models (CBKIT30-40) and the S3M60KX and S3M80KX models (CBKIT30-80).
  • Page 27 4. Operation Operating Mode/Status UPS Power On Description When the UPS is powered on, it will enter into this mode for a few seconds as the CPU and system initialise. LCD Panel No-output Description When bypass voltage/frequency is out of acceptable range or bypass is disabled (or forbidden), the Mode UPS will enter No-output Mode if powering on or turning off the UPS.
  • Page 28 4. Operation AC Mode (continued) ECO Mode Description When the input voltage is within voltage regulation range and ECO Mode is enabled, UPS will bypass voltage to output for energy saving. LCD Panel...
  • Page 29 4. Operation CVCF Mode Description When the output frequency is set to “CF”, the inverter will output constant frequency (50 Hz or 60 Hz). In this mode, the UPS will have no bypass output but still charge the battery. LCD Panel Battery Mode Description When the input voltage/frequency is beyond the acceptable range or experiences a power failure, the...
  • Page 30 4. Operation Battery Mode (continued) Bypass Mode Description When input voltage is within acceptable range and bypass is enabled, turn off the UPS and it will enter Bypass Mode. The alarm will beep every two minutes. LCD Panel Battery Test Description When the UPS is in AC Mode or CVCF Mode, press the “Test”...
  • Page 31 4. Operation Battery Test (continued) Warning Status Description If some errors occur in the UPS (but it is still operating normally), it will show one more screen to represent the warning situation. In the warning screen, the icon will be flashing. It can show up to 3 error codes, with each code indicating one error.
  • Page 32: Fault Codes

    4. Operation 4.9 Fault Codes - When Icon is Solid (Not Flashing) Fault code Fault Event Icon Fault Code Fault Event Icon Bus start failure None DSP communication failure None Bus over None Overload Bus under None Incorrect UPS setting None Bus unbalance None...
  • Page 33: Warning Indicator

    4. Operation 4.10 Warning Indicator- When is Flashing Warning Icon (flashing) Alarm Battery low Beeping every second Overload Beeping twice every second Battery unconnected Beeping every second Over charge Beeping every second EPO enable Beeping every second Fan failure/Over temperature Beeping every second Charger failure Beeping every second...
  • Page 34: Communication

    To enable EPO function, open contacts with pins 1 and 2. 5.3 RS-232 Port The RS-232 port is built into the UPS system’s rear panel (S3M30KX and S3M40KX models) or behind the front door (S3M60KX and S3M80KX models) to provide service support when upgrading the UPS system software.
  • Page 35: Troubleshooting

    6. Troubleshooting If the UPS system does not operate correctly, identify the problem using the table below. Symptom Possible Cause Remedy No indication and alarm in the front display The AC input power is not connected Check to make sure input cable is firmly panel even though the mains is normal.
  • Page 36: Storage And Maintenance

    Higher temperatures shorten fan life. When the UPS is running, make sure all fans are working normally and make sure air can move freely around and through the UPS. If not, replace the fans. Note: Contact Tripp Lite Technical Support for more maintenance information. Do not perform maintenance if you are not qualified to do so.
  • Page 37: Specifications

    93,5% at 100% Resistive Load; 93% at 50% Resistive Load PARALLEL Parallel for Capacity Up to 3 Units Parallel for Redundancy INTERNAL BATTERIES (S3M30KX and S3M40KX include internal batteries. Versions are also available without internal batteries: S3M30KX-NIB and S3M40KX-NIB.) Type 12V Non-Spillable VRLA AGM/GEL Capacity...
  • Page 38 8. Specifications MODELS S3M30KX S3M40KX S3M60KX S3M80KX EXTERNAL BATTERIES (S3M30KX-NIB, S3M40KX-NIB, S3M60KX, S3M80KX require external batteries for backup.) Type 12V Non-Spillable VRLA AGM/GEL DC Nominal Acceptance Voltage ± 240 VDC 40N (N ≥ 1 x Strings of 20 + 20) Quantity Adjustable up to 4A ±...
  • Page 39 8. Specifications Battery Cabinet Dimensions 12V 65/100Ah x 40pcs 12V 40Ah x 40pcs 12V 9/10Ah x 80pcs Dimmensions Battery Cabinet Models Breaker Included (H x W x D) mm Description BP480V100 Battery Cabinet with 40 x 100Ah batteries 400A, 3-Pole Battery Cabinet without batteries, but designed for 40 x 100Ah BP480V100-NIB batteries (includes battery cabling and breaker)
  • Page 40: Warranty

    Seller will repair or replace the defective parts without charge for labor or parts. If the product was not started up by authorised Tripp Lite service, replacement parts will be provided but labor charges will apply based on published Tripp Lite Time and Material Rates. Tripp Lite will assign to you any warranties provided by the manufacturers of components of the Tripp Lite product.