Ac Input/Output Wiring (Parallel Ups – Single Input) - Tripp Lite SmartOnline SU80K Owner's Manual

3-phase ups system
Hide thumbs Also See for SmartOnline SU80K:
Table of Contents

Advertisement

6 – Wiring
(continued)
1
6-8 AC Input/Output Wiring (Parallel UPS – Single Input)
Parallel Configuration Warnings:
2
The total input cable length must be equal to the total
output cable length in order to prevent unbalanced load
sharing between two UPS systems under reserve mode
(i.e. IP1 + OP1 = IP2 + OP2; deviation must be <10%).
3
Parallel configuration only supports 2 UPS systems (1+1
redundancy ). Do not attempt to link more than two UPS
systems via parallel configuration.
The UPS systems must have the same rating and capacity
for parallel configuration installation. Attempting to link
4
dissimilar UPS systems will damage the UPS systems
and create a serious risk of personal injury and property
damage.
Each UPS must have its parallel group set to 2 and a
5
different "Parallel ID" that indicates the UPS systems
are being run in parallel. (See
Follow the steps in
Section
1
in the diagram.
6
Connect the included parallel
2
parallel configuration port
7
8
9
10
11
12
13
Section 9-5-5
for details.)
6-7, wiring the UPS systems as shown
configuration cable
A
to the
B
of each UPS system.
AC I/P
IP1
UPS1
Main I/P
IP2
UPS2
Main I/P
1
B
2
16
OP1
O/P
Parallel Port
Load
O/P
OP2
Parallel Port
B