Carrier 19XR Start-Up, Operation And Maintenance Instructions Manual page 77

Hermetic centrifugal liquid chillers 50/60 hz with pic ii controls and hfc-134a
Hide thumbs Also See for 19XR:
Table of Contents

Advertisement

Custom Alarm/Alert Messages with Troubleshooting Guides (cont)
J. CHILLER ALERTS (cont)
PRIMARY
STATE
MESSAGE
151
CONDENSER PRESSURE
ALERT
152
RECYCLE
ALERT
153
no message:
ALERT only
154
POTENTIAL
FREEZE-UP
155
OPTION SENSOR
FAULT
156
OPTION SENSOR
FAULT
157
OPTION SENSOR
FAULT
158
SENSOR ALERT
159
SENSOR ALERT
160
DIFFUSER
ALERT
*[LIMIT] is shown on the CVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
Table 8 — CVC Primary and Secondary Messages and
SECONDARY
MESSAGE
PUMP RELAY
151->High Condenser
ENERGIZED
Pressure [VALUE]: Pump
Energized to Reduce
Pressure.
EXCESSIVE RECYCLE
152->Excessive recycle starts. Chiller load is too low to keep compressor on
STARTS
no message;
153->Lead/Lag Disabled:
ALERT only
Duplicate Chiller Address;
Check Configuration
COND PRESS/TEMP
154->Condenser freeze up
TOO LOW
prevention
REMOTE RESET
155->Sensor Fault/Option
SENSOR
Disabled:
Remote Reset Sensor
AUTO CHILLED
156->Sensor Fault/Option
WATER RESET
Disabled:
Auto Chilled Water Reset
AUTO DEMAND
157->Sensor Fault/Option
LIMIT INPUT
Disabled:
Auto Demand Limit Input
SPARE TEMPERATURE
158->Spare Temperature #1
#1
[VALUE] exceeded limit of
[LIMIT].*
SPARE TEMPERATURE
159->Spare Temperature #2
#2
[VALUE] exceeded limit of
[LIMIT].*
DIFFUSER
160->Diffuser Position Alert;
POSITION
Check Diffuser Configuration.
ALARM MESSAGE
PRIMARY CAUSE
Check sensor wiring and accuracy.
Check condenser flow and fluid temperature.
Check for fouled tubes. This alarm is not
caused by the High Pressure Switch.
line and there has been more than 5 starts in
4 hours. Increase chiller load, adjust hot gas
bypass, increase RECYCLE RESTART DELTA
T from SETUP1 Screen.
Illegal chiller address configuration in Lead/
Lag screen. Both chillers require a different
address.
The condenser pressure transducer is reading
a pressure that could freeze the condenser
tubes.
Check for condenser refrigerant leaks.
Check fluid temperature.
Check sensor wiring and accuracy.
Place the chiller in PUMPDOWN mode if the
vessel is evacuated.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check diffuser configuration in SETUP2
screen.
77
ADDITIONAL
CAUSE/REMEDY