Carrier 19XR Start-Up, Operation And Maintenance Instructions Manual page 30

Hermetic centrifugal liquid chillers 50/60 hz with pic ii controls and hfc-134a
Hide thumbs Also See for 19XR:
Table of Contents

Advertisement

To access this display from the CVC default screen:
1. Press
MENU
.
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT SERVICE .
4. Press SELECT .
5. Scroll down to highlight SETUP2 .
DESCRIPTION
Capacity Control
Proportional Inc Band
Proportional DEC Band
Proportional ECW Gain
Guide Vane Travel Limit
Diffuser Control
Diffuser Option
Guide Vane 25% Load Pt
Diffuser 25% Load
Guide Vane 50% Load Pt
Diffuser 50% Load Pt
Guide Vane 75% Load Pt
Diffuser 75% Load Pt
Diffuser Full Span mA
VFD Speed Control
VFD Option
VFD Gain
VFD Increase Step
VFD Minimum Speed
VFD Maximum speed
NOTE: No variables are available for CCN read operation; forcing shall be supported on service screens.
To access this display from the CVC default screen:
1. Press
MENU
.
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT SERVICE .
4. Press SELECT .
5. Scroll down to highlight LEADLAG .
DESCRIPTION
Lead Lag Control
LEAD/LAG Configuration
DSABLE=0, LEAD=1,
LAG=2, STANDBY=3
Load Balance Option
Common Sensor Option
LAG Percent Capacity
LAG Address
LAG START Timer
LAG STOP Timer
PRESTART FAULT Timer
STANDBY Chiller Option
STANDBY Percent Capacity
STANDBY Address
NOTE: No variables are available for CCN read or write operation.
Table 2 — CVC Display Data (cont)
EXAMPLE 18 — SETUP2 DISPLAY SCREEN
STATUS
UNITS
2-10
2-10
1-3
30-100
%
0-1
DSABLE/ENABLE
0-78
%
0-100
%
0-78
%
0-100
%
0-78
%
0-100
%
15-22
mA
0/1
DSABLE/ENABLE
0.1-1.5
1-5
%
65-100
%
90-110
%
EXAMPLE 19 − LEADLAG DISPLAY SCREEN
STATUS
UNITS
0-3
0/1
DSABLE/ENABLE
0/1
DSABLE/ENABLE
25-75
%
1-236
2-60
MIN
2-60
MIN
2-30
MIN
0/1
DSABLE/ENABLE
25-57
%
1-236
30
POINT
DEFAULT
gv inc
6.5
gv dec
6.0
gv ecw
2.0
gv lim
80
diff opt
DSABLE
gv 25
25
df 25
0
gv 50
50
df 50
0
gv 75
75
df 75
0
diff ma
18
vfd opt
DSABLE
vfd gain
0.75
vfd step
2
vfd min
70
vfd max
100
POINT
DEFAULT
leadlag
0
load/bal
DSABLE
commsens
DSABLE
lag per
50
lag add
92
lagstart
10
lagstop
10
preflt
5
stndopt
DSABLE
stnd per
50
stnd add
93