19XR PIC II SETUP1 TABLE CONFIGURATION SHEET
DESCRIPTION
Comp Motor Temp Override
Cond Press Override
Comp Discharge Alert
Comp Thrust Brg Alert
Chilled Medium
Chilled Water Deadband
Evap Refrig Trippoint
Refrig Override Delta T
Condenser Freeze Point
Evap Flow Delta P Cutout
Cond Flow Delta P Cutout
Water Flow Verify Time
Oil Press Verify Time
Recycle Control
Recycle Restart Delta T
Recycle Shutdown Delta
SPARE ALERT/ALARM ENABLE
Disable=0, Lo=1/3, Hi=2/4
Spare Temp #1 Enable
Spare Temp #1 Limit
Spare Temp #2 Enable
Spare Temp #2 Limit
RANGE
UNITS
150 to 200
DEG F
90 to 165
PSI
125 to 200
DEG F
165 to 185
DEG F
0/1
WATER/BRINE
.5 to 2.0
^F
0.0 to 40.0
DEG F
2.0 to 5.0
^F
−20 to 35
DEG F
0.5 to 50.0
PSI
0.5 to 50.0
PSI
0.5 to 5
MIN
15 to 300
SEC
2.0 to 10.0
DEG F
0.t to 4.0
DEG F
0 to 4
−40 to 245
DEG F
0 to 4
−40 to 245
DEG F
CL-7
DEFAULT
VALUE
200
125
200
175
WATER
1.0
33
3
34
5.0
5.0
5
40
5
1
0
245
0
245