Carrier 19XR Start-Up, Operation And Maintenance Instructions Manual page 24

Hermetic centrifugal liquid chillers 50/60 hz with pic ii controls and hfc-134a
Hide thumbs Also See for 19XR:
Table of Contents

Advertisement

To access this display from the CVC default screen:
1. Press
MENU
.
2. Press STATUS .
3. Scroll down to highlight POWER .
4. Press SELECT .
DESCRIPTION
Average Line Current
Actual Line Current
Average Line Voltage
Actual Line Voltage
Power Factor
Motor Kilowatts
Motor Kilowatt-Hours
Demand Kilowatts
Line Current Phase 1
Line Current Phase 2
Line Current Phase 3
Line Voltage Phase 1
Line Voltage Phase 2
Line Voltage Phase 3
Ground Fault Phase 1
Ground Fault Phase 2
Ground Fault Phase 3
Frequency
I2T Sum Heat-Phase 1
I2T Sum Heat-Phase 2
I2T Sum Heat-Phase 3
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation.
To access this display from the CVC default screen:
1. Press
MENU
.
2. Press STATUS .
3. Scroll down to highlight ISM STAT .
4. Press SELECT .
DESCRIPTION
ISM Fault Status
Single Cycle Dropout
Phase Loss
Overvoltage
Undervoltage
Current Imbalance
Voltage Imbalance
Overload Trip
Locked Rotor Trip
Starter LRA Trip
Ground Fault
Phase Reversal
Frequency Out of Range
ISM Power on Reset
Phase 1 Fault
Phase 2 Fault
Phase 3 Fault
ICR Start Complete
IM Start/Run Fault
2M Start/Run Fault
Pressure Trip Contact
Starter Fault
Motor Amps Not Sensed
Starter Acceleration Fault
High Motor Amps
ICR Stop Complete
1M/2M Stop Fault
Motor Amps When Stopped
Hardware Failure
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation.
Table 2 — CVC Display Data (cont)
EXAMPLE 6 — POWER DISPLAY SCREEN
STATUS
0-999
0-99999
0-999
0-99999
0.0-1.0
0-99999
0-99999
0-99999
0-99999
0-99999
0-99999
0-99999
0-99999
0-99999
0-999
0-999
0-999
0-99
0-200
0-200
0-200
EXAMPLE 7 — ISM STAT SCREEN
STATUS
0-223
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
0-1
24
UNITS
%
AMPS
%
VOLTS
kW
kWH
kWH
AMPS
AMPS
AMPS
VOLTS
VOLTS
VOLTS
AMPS
AMPS
AMPS
Hz
%
%
%
UNITS
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
FALSE/TRUE
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
FALSET/TRUE
NORMAL/ALARM
NORMAL/ALARM
NORMAL/ALARM
POINT
% AMPS
AMP A
VOLT P
VOLT A
PF
KW A
KWH
DEM KWH
AMPS 1
AMPS 2
AMPS 3
VOLTS 1
VOLTS 2
VOLTS 3
GF 1
GF 2
GF 3
FREQ
HEAT1SUM
HEAT2SUM
HEAT3SUM
POINT
ISMFLT
CYCLE 1
PH LOSS
OV VOLT
UN VOLT
AMP UNB
VOLT UNB
OVERLOAD
LRATRIP
SLRATRIP
GRND FLT
PH REV
FREQFLT
ISM POR
PHASE 1
PHASE 2
PHASE 3
START OK
1M FLT
2M FLT
PRS TRIP
STRT FLT
NO AMPS
ACCELFLT
HIGHAMPS
STOP OK
1M2MSTOP
AMPSTOP
HARDWARE

Hide quick links: