19XR PIC II OPTIONS TABLE CONFIGURATION SHEET
DESCRIPTION
Auto Restart Option
Remote Contacts Option
Soft Stop Amps Threshold
Surge/Hot Gas Bypass
Surge Limit/HGBP Option
Select: Surge=0, HGBP=1
Min. Load Point (T1/P1)
Surge/HGBP Delta T1
Surge/HGBP Delta P1
Full Load Point (T2/P2)
Surge/HGBP Delta T2
Surge/HGBP Delta P2
Surge/HGBP Deadband
Surge Protection
Surge Delta % Amps
Surge Time Period
Ice Build Control
Ice Build Option
Ice Build Termination
0=Temp, 1=Contacts,2=Both
Ice Build Recycle
Refrigerant Leak Option
Refrigerant Leak Alarm mA
RANGE
UNITS
0/1
DSABLE/ENABLE
0/1
DSABLE/ENABLE
40 to 100
%
0/1
0.5 to 15
^F
30 to 170
PSI
0.5 to 15
^F
50 to 170
PSI
0.5 to 3
^F
5 to 15
%
7 to 10
MIN
0/1
DSABLE/ENABLE
0 to 2
0/1
DSABLE/ENABLE
0/1
DSABLE/ENABLE
4 to 20
mA
CL-6
DEFAULT
VALUE
DSABLE
DSABLE
100
0
1.5
50
10
85
1
10
8
DSABLE
0
DSABLE
DSABLE
20