Figure 5.1 Correct and Incorrect gravity drains for downflow and upflow units
Vertiv | Liebert® PDX™ and PCW™ Installer/User Guide |
Table 5.3 Gravity-fed Drain Line Figure Descriptions
Item
Description
1
For downflow units with discharge into a raised floor
2
For upflow and for downflow units with discharge to the front or side
3
Correct drain installation
4
Incorrect drain installation
Internal drain and trap
5
NOTE: Units equipped with a condensate pump do not have an internal trap.
6
External drain
7
Continuous downward slope
8
External trap. Do not trap externally.
9
External traps, although unintentional. Lines must be rigid enough not to bow.
10
Internal drain and trap location. Drain and trap not shown in this view.
32