5.
All wiring must be sized and selected for insulation case per NEC and other local codes.
6.
Do not bend cables to less than four times the diameter of the cable.
7.
Do not deform cables when securing in bundles or when hanging them.
8.
Avoid running the cables by devices that may introduce noise, such as machines, fluorescent lights, and electronics.
9.
Avoid stretching cables.
10. The electrically commutated (EC) motors included in the Liebert MC Condenser are suitable for connection to power supplies with a
solidly grounded neutral or high resistance to ground or corner ground.
a.
Acceptable power supplies for 208 to 575V nominal units:
208V wye with solidly grounded neutral and 120V line to ground;
380V wye with solidly grounded neutral and 220V line to ground;
480V wye with solidly grounded neutral and 277V line to ground;
575V wye with solidly grounded neutral and 332V line to ground (uses step-down transformer);
Wye with high resistance (or impedance) ground;
Delta with corner ground
b.
Unacceptable power supplies for 208V to 575V nominal units:
Delta without ground or with floating ground;
Delta with grounded center tap.
DPN002169
Page :3 /3
LIEBERT MC CONDENSER
ELECTRICAL FIELD CONNECTIONS
PREMIUM EFFICIENCY CONTROL
REV : 10