Liebert PX018 Installer's/User's Manual page 31

Pdx and pcw series thermal management systems, 3 to 8 ton (11 to 29 kw) capacity, upflow and downflow, 60 hz
Table of Contents

Advertisement

Observe the following requirements and refer to Figure 5.1 on the next page, when installing and routing
the drain line:
The drain line must be sized for 2 gpm (7.6 l/m) flow.
The drain line must be located so it will not be exposed to freezing temperatures.
The drain should be the full size of the drain connection.
The drain line must slope continuously away from the unit. Pitch drain line toward drain a
minimum of 1/8 in. (3 mm) per 1 ft (305 mm) of length.
Drain is trapped internally. Do not externally-trap the drain line.
The drain line must be rigid enough that it does not sag between supports, which
unintentionally creates traps.
Use copper or other material suitable for draining water that can reach temperatures up to
212°F (100°C).
The drain line must comply with all applicable codes.
When the evaporator is installed below the level of the gravity-fed drain line, the optional
condensate pump kit is required. See the appropriate section, depending on the configuration
of your unit:
Factory-installed Condensate Pump in Upflow Units
Field-installed Condensate Pump for Downflow Units
Vertiv | Liebert® PDX™ and PCW™ Installer/User Guide |
on page 33
on page 33
31