Mitsubishi LGH-15RX5-E Handbook page 38

Table of Contents

Advertisement

(10) Setting of function selection switches (SW1, 2, and 5)
The associated switches are as listed below.
* This function can also be set from PZ-60DR-E. When the function has been switched from the remote con-
troller later on, the system will operate according to the setting of the remote controller.
Type
SW1
Main/Sub selection switch
SW2 1
Trial operation
2
Pulse input *
3
Power supply/exhaust when
operation starts *
4
SA fan fixed at Low speed *
5
EA fan fixed at Low speed *
6
Power supply ON/OFF *
Note 2
7
Bypass ventilation priority at
Automatic mode *
Temperature condition for
Night purge operation
8
TM4 9, 0 output setting
9
Supply Extra High/High *
10
Exhaust Extra High/High *
SW5 1
Delay setting *
Note 2
2
Operation output monitor *
3
Exhaust fan stop during air
conditioner defrost *
Exhaust fan Low fan speed at
outdoor air temperature of -
15ºC or lower *
4
Automatic recovery after
power failure *
Note 2
5
Filter cleaning setting *
Note 2
6
TM3 6, 7 output setting
7
Interlock mode setting *
Note 2
8
Name
Lossnay control mode (Main/Sub) switching (The factory setting is set
to "Main".)
ON : Trial operation mode
OFF: Normal mode (Factory setting)
ON : At time of pulse signal input (Requires a pulse width of 200 ms or
OFF: At time of Level signal and Mr. Slim signal inputs (Factory setting)
ON : Power supply exhaust mode
OFF: Normal mode (Factory setting)
ON : Low fan speed fixed
OFF: Normal mode (Factory setting)
ON : Low fan speed fixed
OFF: Normal mode (Factory setting)
ON : Enable
OFF: Disable (Factory setting)
ON : Automatic ventilation outdoor air cooling priority mode / Night
OFF: Automatic ventilation normal mode / Night purge operation condi-
ON : Operation monitor output with delay function 1. Refer to (3) 2
OFF: Operation monitor output based on SW5-2 (Factory setting)
ON : Supply air fan Extra High fan speed
OFF: Supply air fan High fan speed (Factory setting)
ON : Exhaust air fan Extra High fan speed
OFF: Exhaust air fan High fan speed (Factory setting)
ON : Delay operation of 30 minutes
OFF: Normal (Factory setting)
ON : Operation monitor output correspond to air supply fan
OFF: Operation monitor output with normal operation (Factory setting)
ON : Both Exhaust air fan and Supply air fan (Low fan speed) opera-
OFF: Exhaust fan operation (Only Supply air fan stopped) (Factory set-
ON : After the recovery, operation at the mode preceding the power
OFF: Stop after the recovery (Factory setting)
Selection switch for accumulated running time of the filter cleaning dis-
play.
ON : 3,000 hours
OFF: No filter maintenance display (Factory setting)
ON : Operation monitor output with delay functions 2. Refer to (3) 2
OFF: Bypass ventilation operation monitor output (Factory setting)
Effective only at time of external control input usage.
Refer to (5) 2 Interlock mode (page 32).
greater)
purge operation condition of outdoor air temperature is 17ºC or
higher (within 24 hours)
tion of outdoor air temperature is 28ºC or higher (within 24 hours)
(Factory setting)
Fan speed control by function setting (page 26), and (6) 1
Output terminals (page 33).
tion at outdoor air temperature of -15ºC or lower
ting)
failure
Fan speed control by function setting (page 26), and (6) 1
Output terminals (page 33).
— 38 —
Specification