2 Interlock mode
Lossnay can set the following 4 types of interlock modes for the start/stop signal from the external device.
Interlock
Pulse signal input
mode
ON/OFF
The start/stop condition
interlock
will be reversed each
(Remote
time the pulse signal is
controller
input.
last touch
operation
permitted)
ON interlock
Lossnay will start when
the pulse signal is
input.
Stopping is by remote
controller.
OFF inter-
Lossnay will stop when
lock
the pulse signal is input.
Starting is by remote
controller.
External
Same as ON/OFF inter-
input priority
locked.
ON/OFF
interlock
*1: Display of LCD when setting is by PZ-60DR-E remote controller
3 Delay operation
This function delays the starting of Lossnay for 30 minutes with respect to the start signal from the external
device (and for 10 to 60 minutes when using PZ-41SLB-E). When using remote controllers other than PZ-
41SLB-E, LED1 on the Lossnay circuit board will light during delay operation. Also, when using PZ-60DR-E
and PZ-41SLB-E, there will be a display of the delay time.
Function settings
(Remote controller func-
Normal operation
Delay operation setting
"oFF"
(Factory setting)
Delay operation
Delay operation setting
"on"
Note that delay operation will be disabled under the following condition
G When the start signal from the external device is a pulse signal.
G When the system is interlocked with Mr. Slim or City Multi indoor units set to the fan operation mode.
G When the system is restarted within 2 hours of Lossnay stop.
G When the interlock mode is set to "OFF Interlock".
Other than pulse signal
Lossnay will start with
the operation signal of
the external device, and
Lossnay will stop with
the stop signal.
Lossnay will start with
the start signal of the
external device.
Stopping is by remote
controller.
Lossnay will stop with
the stop signal of the
external device.
Starting is by remote
control.
Same as ON/OFF inter-
locked.
Note that during opera-
tion that started with a
signal from the external
device, stopping by
remote controller will
not be possible.
PZ-60DR-E
(Delay starting time)
tion selection)
0 minutes
(Factory setting)
10 to 60 minutes (in 10-
minute units)
PZ-60DR-E
input
(Remote controller
function selection)*1
Interlock mode
setting selection
"onoF"
(Factory setting)
Interlock mode
setting
"on"
Interlock mode
setting
"oFF"
Interlock mode
setting
"oUT"
Setting Method
PZ-41SLB-E
SW5-1: OFF
(Factory setting)
SW5-1: ON
— 32 —
Setting Method
PZ-52SF-E or remote
PZ-41SLB-E
controller not used
(Interlock
(Function selec-
mode)
1
SW5-7: OFF
(Factory
SW5-8: OFF
setting)
(Factory setting)
2
SW5-7: ON
SW5-8: OFF
3
SW5-7: OFF
SW5-8: ON
4
SW5-7: ON
SW5-8: ON
PZ-52SF-E or remote
controller not used
(Function selection switch)
tion switch)