Mitsubishi LGH-15RX5-E Handbook page 26

Table of Contents

Advertisement

2Fan speed control by function setting
The following fan speed control can be set with PZ-60DR-E or the function selection switch (SW2) on the
Lossnay circuit board.
Function
Extra High
This switches the settable fan speed from the remote controller
/High
and the system controller. Set this when there is a need for
Fan speed
large air volume, or when there is a long duct line.
selection
When set to High fan speed, High/Low fan speed can be set,
and when set to Extra High fan speed, Extra High/Low fan
speed can be set.
Display
Multiple
units
Multi venti-
This switches the settable fan speed from the remote controller
lation
and the system controller to a fixed Low fan speed. The sup-
mode
ply/exhaust balance is adjusted to suit the usage environment
or the place of installation.
Operation
Multiple
units
Power
During the first 30 minutes of operation, operation will be at
supply/
High (Extra High) fan speed. This is used when rapid ventila-
exhaust
tion is desired at the time of starting operation.
mode
After 30 minutes have elapsed since starting operation, or
(When
when the fan speed set from the remote controller or the sys-
operation
tem controller has been changed to something other than High
starts )
fan speed, power ventilation will be cancelled and the system
will follow the fan speed set by the remote controller or system
controller.
Display
Multiple
units
Details
The fan speed display of the remote controller,
and the system controller will be the same for
either Extra High or High.
When PZ-60DR-E will not be used in a system of
multiple Lossnay units, set the function selection
switches on the Lossnay circuit board for each
unit.
When both supply and exhaust are set to the multi
ventilation mode, due to operation restrictions PZ-
60DR-E cannot be switched to a setting other
than Low/Extra Low fan speed. Other remote con-
trollers and system controllers can change the fan
speed display; however, the fan will remain fixed
at Low fan speed.
When PZ-60DR-E will not be used in a system of
multiple Lossnay units, set the function selection
switches on the Lossnay circuit board for each
unit.
During power ventilation, PZ-60DR-E will display
"POWER VENT START". Other remote controllers
and system controllers will display the set fan
speed, even during power supply exhaust opera-
tion.
When PZ-60DR-E will not be used in a system of
multiple Lossnay units, set the function selection
switches on the Lossnay circuit board for each
unit.
— 26 —
Setting Method
PZ-60DR-E
PZ-60DR-E Not Used
(Remote controller
(Function selec-
function selection)
tion switch)
Supply fan
Air supply SW2-9
speed setting
: ON
Extra High SH: L
Exhaust SW2-10
High
H: L
: ON
Exhaust fan
speed setting
(Refer to page
Extra High SH: L
38)
High
H: L
(Refer to page
41)
Supply fan
Air supply SW2-4
speed setting
: ON
Multiple ventila-
Exhaust SW2-5
tion
: L
: ON
Exhaust fan
speed setting
(Refer to page
Multiple ventila-
38)
tion
: L
(Refer to page
41)
Power supply/
SW2-3: ON
exhaust when
operation starts :
(Refer to page
ON
38)
(Refer to page
41)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents