Mitsubishi LGH-15RX5-E Handbook page 37

Table of Contents

Advertisement

Night Purge mode is active; no operation
No
No
Temperature monitoring
operation (5 minutes)
Night Purge operation
*1: When Lossnay is interlocked with the City Multi indoor units, "Stop of Lossnay during interlocked operation
with the City Multi operating in cooling mode" is another necessary condition in addition to that of "Detection
of an outdoor temperature of 17 ºC or 28 ºC or higher (within 24 hours)".
(Night Purge operation will be performed when either of these necessary conditions has been satisfied.)
1:00 A.M.
Yes
Outdoor
temperature 17ºC/28ºC
or more (within 24
hours)
Yes
Indoor
temperature > 22ºC and
Indoor temperature
- Outdoor temperature
> 5ºC
Yes
(Bypass ventilation)
No
6:00 A.M.
Yes
Finish Night Purge
operation (Stop)
The outdoor temperature (OA) setting can be selected either 17ºC or
28ºC by using Dip-Switch (SW2-7) in the Lossnay control box.
Refer to the remote controller installation manual for more information.
*1
No
55-minute stop
Night Purge
operating
No
— 37 —
Yes